Mounting the <strong>apC</strong>/<strong>8X</strong><br />

Connecting the Advanced Power System (apS)<br />

The apS is an optional 1 power supply unit that provides uninterrupted power<br />

backup for the <strong>apC</strong>/<strong>8X</strong>. It has knockouts that line up directly to those on the<br />

<strong>apC</strong>/<strong>8X</strong>, and compatible terminal blocks and cable harnesses that keep wiring<br />

to a minimum (see Figure 3.5).<br />

+<br />

-<br />

+ -<br />

Battery<br />

Fuse<br />

AC Fault<br />

Output<br />

Low Battery<br />

Fault Output<br />

AC Input<br />

AC Input<br />

Fuse<br />

LED<br />

120 V AC<br />

50/60 Hz<br />

<strong>apC</strong>/<strong>8X</strong><br />

12 volt 17 ah 12 volt 17 ah<br />

Battery<br />

Battery<br />

apS Main Board<br />

Figure 3.5: apS Connection to <strong>apC</strong>/<strong>8X</strong><br />

Note:<br />

Battery cables are not power limited and should be isolated from<br />

all other cabling by a minimum of 1/4”. Route the battery cables<br />

away from all other wires.<br />

The apS provides two relay outputs for connecting inputs to the <strong>apC</strong>/<strong>8X</strong>.<br />

• One relay is connected to the MAIN FAIL input on the <strong>apC</strong>/<strong>8X</strong> and<br />

indicates when AC power is lost.<br />

• The second output is connected to the MAIN BATT input on the <strong>apC</strong>/<strong>8X</strong><br />

and indicates low battery voltage or impending loss of backup power.<br />

LEDs on the cabinet door of the apS indicate AC power loss and the state of<br />

the battery charge as relative battery voltage level.<br />

The apS low battery fault and power fault outputs can be looped together and<br />

attached to the apS fail on the <strong>apC</strong>/<strong>8X</strong> or tied to separate monitor points on<br />

the <strong>apC</strong>/<strong>8X</strong>.<br />

1. The apS is optional only in UL294 access control applications. The apS, or some other<br />

UL-Listed Class 2 power-limited UL603 or UL294 power source (with the necessary<br />

standby capability) is required for UL1076 applications.<br />

<strong>apC</strong>/<strong>8X</strong> Installation and Configuration Guide 3-7