Mounting the <strong>apC</strong>/<strong>8X</strong><br />
Connecting the Advanced Power System (apS)<br />
The apS is an optional 1 power supply unit that provides uninterrupted power<br />
backup for the <strong>apC</strong>/<strong>8X</strong>. It has knockouts that line up directly to those on the<br />
<strong>apC</strong>/<strong>8X</strong>, and compatible terminal blocks and cable harnesses that keep wiring<br />
to a minimum (see Figure 3.5).<br />
+<br />
-<br />
+ -<br />
Battery<br />
Fuse<br />
AC Fault<br />
Output<br />
Low Battery<br />
Fault Output<br />
AC Input<br />
AC Input<br />
Fuse<br />
LED<br />
120 V AC<br />
50/60 Hz<br />
<strong>apC</strong>/<strong>8X</strong><br />
12 volt 17 ah 12 volt 17 ah<br />
Battery<br />
Battery<br />
apS Main Board<br />
Figure 3.5: apS Connection to <strong>apC</strong>/<strong>8X</strong><br />
Note:<br />
Battery cables are not power limited and should be isolated from<br />
all other cabling by a minimum of 1/4”. Route the battery cables<br />
away from all other wires.<br />
The apS provides two relay outputs for connecting inputs to the <strong>apC</strong>/<strong>8X</strong>.<br />
• One relay is connected to the MAIN FAIL input on the <strong>apC</strong>/<strong>8X</strong> and<br />
indicates when AC power is lost.<br />
• The second output is connected to the MAIN BATT input on the <strong>apC</strong>/<strong>8X</strong><br />
and indicates low battery voltage or impending loss of backup power.<br />
LEDs on the cabinet door of the apS indicate AC power loss and the state of<br />
the battery charge as relative battery voltage level.<br />
The apS low battery fault and power fault outputs can be looped together and<br />
attached to the apS fail on the <strong>apC</strong>/<strong>8X</strong> or tied to separate monitor points on<br />
the <strong>apC</strong>/<strong>8X</strong>.<br />
1. The apS is optional only in UL294 access control applications. The apS, or some other<br />
UL-Listed Class 2 power-limited UL603 or UL294 power source (with the necessary<br />
standby capability) is required for UL1076 applications.<br />