Figure 6. Wall Assembly, Nunavik, Quebec<br />
Source: Angers (1999).<br />
Figure 7. Floor Assembly, Nunavik, Quebec<br />
Source: Angers (1999).<br />
• Floor: The floor (Figure 6) is a double system, which creates a service chase for the<br />
air ducts of an oil heating system. The thermal resistance of the double floor system is<br />
RSI-6.7 (R-38) for public buildings or RSI-5.4 (R-31) for houses. In southern<br />
Quebec, RSI-4.7 (R-27) is required for floors.<br />
• Windows: Triple-glazed windows provide thermal resistance of RSI-0.5 (R-3) as<br />
compared to double-glazed windows in southern Quebec. Window openings are<br />
reduced to a minimum.<br />
PERD-079: Task 2 - <str<strong>on</strong>g>Literature</str<strong>on</strong>g> <str<strong>on</strong>g>Review</str<strong>on</strong>g> 24