Roof: With a shallow-pitched south-facing single plane framed with 400 mm (16 in.) I-<br />
beam rafters, the so-called “cool roof” c<strong>on</strong>sisted of two layers of exterior roof sheathing<br />
s<strong>and</strong>wiching a vent channel. The lower layer of sheathing was vapour-permeable<br />
structural fibreboard <strong>and</strong> the upper layer was OSB. The roofing was st<strong>and</strong>ing-seam<br />
galvanized steel. The roof was insulated with 300 mm (12 in.) blown-in fibreglass with a<br />
total of RSI-10.6 (R-60). Future additi<strong>on</strong>s might include uni-solar peel-<strong>and</strong>-stick<br />
photovoltaic modules to be installed <strong>on</strong> the metal roof.<br />
Ventilati<strong>on</strong>: A heat-recovery ventilator with a damper c<strong>on</strong>troller allowed the homeowner<br />
to select between two possible air intake ducts depending <strong>on</strong> the outdoor temperature.<br />
One air intake duct, an “earth tube,” was a 30 m (100 ft.) l<strong>on</strong>g polyvinyl chloride (PVC)<br />
duct buried in the ground. The HRV c<strong>on</strong>troller regulated ventilati<strong>on</strong> air intake as follows.<br />
For an outdoor temperature of less than 13ºC (55ºF), ventilati<strong>on</strong> air is drawn through the earth<br />
tube, where it is heated by the soil.<br />
For an outdoor temperature greater than 13ºC (55ºF), but less than the indoor air temperature,<br />
ventilati<strong>on</strong> air is drawn through the c<strong>on</strong>venti<strong>on</strong>al outdoor air intake grille.<br />
When the outdoor temperature equals the indoor air temperature, the heat recovery functi<strong>on</strong> is<br />
bypassed.<br />
For an outdoor temperature greater than the indoor air temperature, ventilati<strong>on</strong> air is drawn<br />
through the earth tube, where it is cooled by the relatively cool soil.<br />
<strong>Heating</strong>: A 1000-watt (3141 Btu/h) electric resistance element, installed in the HRV,<br />
heated the house.<br />