Second, in some cases, the length over which the largest amount of prestressing <strong>for</strong>ce was<br />

transferred appeared to be a distance somewhat less than the original transfer length discussed in<br />

Chapter 5. Figure C.26 shows test G1A-East as an example of the strand stress increase in the<br />

transfer length region as well as the apparent reduction in transfer length. The embedment length<br />

on this test was only 67 inches. The “lone” triangle plots the maximum stress in the strand at the<br />

point of loading at the girder’s ultimate load. This actual plot of strand stress differs<br />

significantly from the theoretical diagram which would go linearly from “0” to the triangle.<br />

300<br />

Stress in Strands (ksi)<br />

250<br />

200<br />

150<br />

100<br />

50<br />

0<br />

0 10 20 30 40 50 60 70 80<br />

Distance From Girder End (Inches)<br />

Strand Yield Stress at Load Point<br />

Strand Maximum Stress at Load Point<br />

Strand Maximum Stress<br />

Effective Prestress<br />

Crack Locations<br />

Figure C.26 G1A-East Strand Stress vs. Distance from Girder End<br />

Figure C.27 shows typical CSS data corresponding with applied shear levels, the location<br />

of shear cracks crossing the bottom strands, and the transfer length region. CSS data was plotted<br />

because it provided a measure of crack growth and allowed identification of the cracks that were<br />

increasing most significantly in size. Comparing crack locations with the resulting end slip<br />

allowed determination of the region where shear cracking most significantly impacted strand<br />

slip. Based on crack location, a comparison was made between strand slip in girders with single<br />

and double density shear rein<strong>for</strong>cement.<br />

C-17