FOR MODELS: JG AND JGA SECTION 1 - DESIGN SPECIFICATIONS & DATA<br />
Optional Main Bearing Temperature Instrumentation -<br />
Alarm & Shutdown<br />
Eutectic Temperature Valve<br />
This eutectic alloy device is selected to melt at 228°F (109°C) to vent control pressure and<br />
to provide a shutdown signal. Upon melting, the fuse rod must be replaced. To ensure<br />
proper operation of the detector, replace the fuse rod every five years.<br />
Electrical Instrumentation Setting<br />
Set within 10% of normal operating temperature, to a maximum of 220°F (104°C) alarm and<br />
230°F (110°C) shutdown.<br />
11/01 PAGE 1 - 23