. Input TypesThe following one byte codes designate the various input types accepted by the <strong>12LS</strong>:Code Input Type------------ ---------------00 Linear (0-60 mV)01 J Thermocouple02 K Thermocouple03 T Thermocouple04 [ Spare ]05 [ Spare ]06 RTD07 Frequency (Pulse Counter). Output TypesOutput type codes are one byte hexadecimal designations formed by setting the individual bits, asexplained below, to their proper state.___7______6______5______4______3______2______1______0____|Cntrl | On | | | |Auto |Digital| DZC ||Action| / | | | | / | / | / || | Off| | | |<strong>Manual</strong>|Analog| TP ||______|______|______|______|______|______|______|______|| | | | | || | | | || | | | 0 = Distributed| | | | Zero Crossing| | | | (DZC)| | | | || | | | 1 = Cycle Time| | | | Proportioned| | | || | | 0 = Digital Output| | | 1 = Analog Output| | || | 0 = PID Control ON| | 1 = PID Control OFF| || 0 = ON/OFF Control Disabled| 1 = ON/OFF Control Enabled|0 = <strong>Rev</strong>erse Acting Output1 = Direct Acting Output8-3