3.3.5 INPUT SCALINGThe ANAFAZE <strong>12LS</strong> contains an area that can be used to install resistors to scale input voltages <strong>and</strong> convert milliampinputs to match the -10 to 60mv (-16.7% to 100%) input range. The input circuit is designed to enable connection ofcurrent inputs (such as 4 to 20ma), <strong>and</strong> voltage inputs. ANAFAZE will supply input scaling as needed -- order option<strong>12LS</strong>-SI-XX. The input circuit is shown below:The location of RA <strong>and</strong> RB for each input is shown on the following table:is shorted by a jumper on the PC board, remove this jumper to install RA.RAResistors should be 0.1% metal film, 1/4 watt. Note that the resistors must be stood on end due to the compact size ofthe unit. Other components such as capacitors can be installed for signal conditioning. Please consult ANAFAZE.The PC board silk screen shows the resistor locations.3-11