SECTION 19 - EXPANSION JOINT AT ROOF (STEEL BEAM)<br />

SECTION 17 - EXPANSION JOINT AT ROOF (MASONRY WALL)<br />

6<br />

65 mm (2 1 90 mm (3<br />

/2”) MIN. FOR 75 mm (3”) SHOE (TYP.)<br />

1 /2”) MIN. FOR 100 mm (4”) SHOE (TYP.)<br />

DO NOT WELD THE SHOE<br />

ON EMBEDED MATERIAL<br />

12 mm ( 1/2”) Ø ROD x 600 mm (24”)<br />

@ 600 mm (24”) c /c<br />

GREASE OR WRAP THIS END<br />

OF ROD WITH BUILDING PAPER<br />

90 mm (3 1 /2”) MIN. FOR 100 mm (4”) SHOE (TYP.)<br />

FIBRE BOARD 12 mm ( 1 /2”)<br />

FIBRE BOARD 12 mm ( 1/2”)<br />

**<br />

12 mm ( 1/2”) Ø ROD x 600 mm (24”)<br />

@ 600 mm (24”) c/c.<br />

5 mm (<br />

GREASE OR WRAP THIS END<br />

OF ROD, WITH BUILDING PAPER<br />

3/16”) 40 mm (1 1 /2”)<br />

WELDED WIRE-MESH<br />

DO NOT WELD THE SHOE ON THE BEAM<br />

WELDED WIRE-MESH<br />

SLAB<br />

(T)<br />

NOMINAL<br />

JOIST DEPTH<br />

(D)<br />

NOMINAL<br />

JOIST DEPTH SLAB<br />

(D) (T)<br />

CEILING EXTENSION<br />

CEILING EXTENSION<br />

T + 6 mm ( 1 /4”)<br />

TOP OF BEARING<br />

CEILING EXTENSION<br />

T + 6 mm ( 1 /4”)<br />

TOP OF BEARING<br />

TYPICAL DETAILS<br />

CEILING EXTENSION<br />

STEEL BEAM, ACCORDING<br />

TO THE SPECIFICATIONS OF<br />

SOLID MASONRY WALL, ACCORDING<br />

TO THE SPECIFICATIONS<br />

OF THE CONSULTING ENGINEER<br />

(FILL THE MASONRY BLOCK WITH<br />

MORTAR, UNDER THE JOIST SHOE)<br />

REBAR (IF REQUIRED BY<br />

THE CONSULTING ENGINEER)<br />

THE CONSULTING ENGINEER (U.N.O)<br />

T + 6 mm ( 1 /4”) = SLAB THICKNESS + SHOE THICKNESS<br />

** WELD THE JOIST TO THE STEEL BEAM OR WITH THE AGREEMENT OF THE<br />

CONSULTING ENGINEER, USE 2-HILTI (X-EDNI 22P8) OR EQUIVALENT, INSTALLED<br />

ACCORDING TO THE MANUFACTURING SPECIFICATIONS.<br />

T + 6 mm ( 1 /4”) = SLAB THICKNESS + SHOE THICKNESS<br />

SECTION 20 - MINIMUM CLEARANCE FOR OPENING<br />

AND HOLE IN THE SLAB<br />

SECTION 18 - EXPANSION JOINT AT INTERMEDIATE FLOOR<br />

(STEEL BEAM)<br />

DIAMETER � 200 mm (8”)<br />

**REBAR AROUND THE HOLE IS NOT REQUIRED<br />

**THE QUANTITY OF HOLE AT 6” AND MORE<br />

OF THE JOIST IS NOT IMPORTANT<br />

150 mm (6”) 150 mm (6”)<br />

MIN. MIN.<br />

OPENING<br />

SEE TYPICAL<br />

REINFORCEMENT<br />

FOR SLAB OPENING.<br />

150 mm (6”)<br />

MIN.<br />

END OF<br />

SLAB<br />

FIBRE BOARD 12 mm (<br />

DO NOT WELD THE SHOE ON THE ANGLE<br />

1/2”)<br />

65 mm (2 1 90 mm (3<br />

/2”) MIN. FOR 75 mm (3”) SHOE (TYP.)<br />

1 /2”) MIN. FOR 100 mm (4”) SHOE (TYP.)<br />

5 mm ( 3 /16”) 40 mm (1 1 /2”)<br />

**<br />

WELDED WIRE-MESH<br />

(T)<br />

SLAB<br />

HOLE<br />

WELDED WIRE-MESH<br />

(D)<br />

NOMINAL<br />

JOIST DEPTH<br />

( 3/4”) 19 mm<br />

(APPLICABLE<br />

AT EACH CASE)<br />

( 3/4”) 19 mm<br />

(APPLICABLE<br />

AT EACH CASE)<br />

NOMINAL<br />

JOIST DEPTH SLAB<br />

(D) (T)<br />

STIFFENER<br />

STIFFENER<br />

STIFFENER<br />

(IF REQUIRED)<br />

CEILING EXTENSION<br />

T + 6 mm ( 1 /4”)<br />

TOP OF BEARING<br />

SUPPORT ANGLE, ACCORDING<br />

TO THE SPECIFICATIONS OF THE<br />

CONSULTING ENGINEER (U.N.O)<br />

CEILING EXTENSION<br />

STEEL BEAM, ACCORDING<br />

TO THE SPECIFICATIONS OF<br />

THE CONSULTING ENGINEER<br />

T + 6 mm ( 1 /4”) = SLAB THICKNESS + SHOE THICKNESS<br />

** WELD THE JOIST TO THE STEEL BEAM OR WITH THE AGREEMENT OF THE<br />

CONSULTING ENGINEER, USE 2-HILTI (X-EDNI 22P8) OR EQUIVALENT, INSTALLED<br />

ACCORDING TO THE MANUFACTURING SPECIFICATIONS.