SECTION 19 - JOIST PARALLEL TO EXPANSION JOINT<br />
SECTION 17 - EXPANSION JOINT AT ROOF (AT STEEL BEAM)<br />
18<br />
65 mm (2 1 /2”) MIN. FOR 75 mm (3”)<br />
OR FOR 100 mm (4”) SHOE (TYP.)<br />
40 mm (1 1 /2”)<br />
5 mm ( 3/16”)<br />
NOMINAL<br />
SLAB (T)<br />
TOTAL<br />
SLAB<br />
FIBRE BOARD 12 mm ( 1 75 mm (3”) MIN.<br />
DO NOT WELD THE STEEL DECK<br />
TYP.<br />
ON THE EMBEDED MATERIAL<br />
/2”) WELDED WIRE-MESH<br />
FIBRE BOARD 12 mm ( 1 /2”)<br />
12 mm ( 1 /2”)Ø ROD x 600 mm (24”)<br />
@ 600 mm (24”) c /c<br />
GREASE OR WRAP THIS END<br />
OF ROD WITH BUILDING PAPER<br />
NOMINAL<br />
SLAB<br />
(T)<br />
DO NOT WELD THE<br />
SHOE ON THE BEAM<br />
STEEL DECK<br />
WELDED WIRE-MESH<br />
NOMINAL<br />
JOIST DEPTH<br />
(D)<br />
STEEL DECK<br />
TOTAL<br />
SLAB<br />
SOLID MASONRY WALL,<br />
ACCORDING TO THE SPECIFICATIONS<br />
OF THE CONSULTING ENGINEER<br />
T + 38 mm (1 1 /2”)<br />
TOP OF BEARING<br />
NOMINAL<br />
JOIST DEPTH<br />
(D)<br />
T + 38 (1 1 /2”)<br />
TOP OF BEARING<br />
TYPICAL DETAILS<br />
REBAR<br />
(IF REQUIRED BY<br />
THE CONSULTING ENGINEER)<br />
CEILING EXTENSION<br />
CEILING EXTENSION<br />
STEEL BEAM ACCORDING TO<br />
THE SPECIFICATIONS OF THE<br />
CONSULTING ENGINEER (UNO)<br />
SECTION 20 - JOIST PARALLEL TO A MASONRY WALL<br />
OR CONCRETE WALL<br />
SECTION 18 - MINIMUM CLEARANCE FOR OPENING<br />
AND HOLE IN THE SLAB<br />
STEEL DECK ANCHORED<br />
TO THE WALL<br />
WELDED WIRE-MESH<br />
50 mm (2”) MIN.<br />
TYP.<br />
NOMINAL<br />
SLAB (T)<br />
TOTAL<br />
SLAB<br />
DIAMETER � 200 mm (8”)<br />
** REBAR AROUND THE<br />
HOLE IS NOT REQUIRED<br />
** THE QUANTITY OF HOLE<br />
AT 150 mm (6”) & MORE<br />
OF THE JOIST IS<br />
NOT IMPORTANT<br />
150 mm (6”)<br />
MIN.<br />
150 mm (6”)<br />
MIN.<br />
OPENING<br />
SEE TYPICAL<br />
REINFORCEMENT<br />
FOR SLAB OPENING.<br />
150 mm (6”)<br />
MIN.<br />
NOMINAL<br />
JOIST DEPTH<br />
(D)<br />
STEEL DECK<br />
SOLID MASONRY WALL OR REINFORCED CONCRETE<br />
WALL, ACCORDING TO THE SPECIFICATIONS<br />
OF THE CONSULTING ENGINEER<br />
T + 38 mm (1 1 /2”)<br />
TOP OF BEARING<br />
NOMINAL<br />
SLAB<br />
(T)<br />
20 mm ( 3 /4”) MIN.<br />
APPLICABLE<br />
IN EACH CASE<br />
20 mm ( 3 /4”) MIN.<br />
APPLICABLE<br />
IN EACH CASE<br />
END OF<br />
SLAB<br />
TOTAL<br />
SLAB<br />
HOLE<br />
REBAR<br />
(IF REQUIRED BY THE<br />
CONSULTING ENGINEER)<br />
NOMINAL<br />
JOIST DEPTH<br />
(D)<br />
STEEL DECK<br />
WELDED WIRE-MESH<br />
TEMPORARY<br />
SUPPORT<br />
(DESIGNED<br />
& SUPPLIED<br />
BY OTHERS)