3.4. Connection to power supply<br />
Warning! A qualified electrician must make the connection to the mains supply.<br />
The 9/12/22kW e-Brick requires a 3-Phase mains supply with a Protective Earth connection<br />
(3P+E); note that no neutral connection is made.<br />
The 3.6kW e-Brick requires a single-phase mains supply with a Protective Earth connection.<br />
All variants require:<br />
1) Permanently installed wiring fed by a suitably rated Miniature Circuit Breaker (MCB) to protect<br />
each phase of the incoming mains supply cable <strong>and</strong> allow isolation of an individual e-Brick. For<br />
North America <strong>and</strong> Canada Moulded Case Circuit Breakers (MCCB) shall be used for branch<br />
circuit protection.<br />
2) A suitably rated supply disconnection device to allow isolation of the mains supply to the e-<br />
Brick <strong>installation</strong>. It is recommended that this shall be easily accessible by the operator.<br />
3.4.1. Essential electrical <strong>installation</strong> data<br />
Refer to Table 3 for peak mains supply current, suggested minimum supply cable cross<br />
sectional area <strong>and</strong> MCB ratings for e-Brick product variants. These recommendations are<br />
in accordance with BS7671:2001 Table 4D2A reference method 11.<br />
e-Brick variant Current / phase (A) Supply cable<br />
size (mm 2 )<br />
MCB rating (A)<br />
3.6kW 20 4 20<br />
9kW 20 4 25<br />
12kW 25 4 25<br />
22kW 57 16 63<br />
Table 3: Supply connection specification<br />
Advice! Every e-Brick system is supplied with an electrical wiring diagram containing system<br />
specific <strong>installation</strong> information.<br />
Advice! Electrical <strong>installation</strong> st<strong>and</strong>ards vary worldwide <strong>and</strong> local regulations shall be observed.<br />
3.4.2. Residual current devices<br />
The internal EMC filters of the e-Brick are designed with a maximum earth leakage of 20mA;<br />
this should be taken in to account when specifying residual current protection devices.<br />
3.5. General recommendations<br />
If you experience difficulties in setting up this product, contact <strong>GEW</strong> at the address given at the<br />
front of this <strong>manual</strong>. If in doubt, ask! We are always ready to help.<br />
3.5.1. Installation<br />
e-Brick systems should be installed by <strong>GEW</strong> service technicians or, alternatively, by <strong>GEW</strong><br />
factory trained personnel. To validate the system warranty, a system specific code must be<br />
entered on completion of <strong>installation</strong> <strong>and</strong> commissioning. When a system has not been<br />
commissioned by <strong>GEW</strong>, a message will appear on the HMI every 20 hours reminding the<br />
customer that the system is not under warranty:<br />
“SYSTEM NOT UNDER WARRANTY. PLEASE CONTACT <strong>GEW</strong>, TEL: +44 (0)1737 824510”<br />
To validate the warranty, enter the password supplied by <strong>GEW</strong> service.<br />
<strong>GEW</strong> <strong>UV</strong> e-Brick <strong>installation</strong> <strong>and</strong> operating <strong>manual</strong> 17 of 49