Programming<br />

When using a HYDROVAR Single drive there are fewer software features available than with the HY-<br />

DROVAR Master drive. All parameters which are not active for the HYDROVAR Single drive are marked with<br />

the following symbol:<br />

S<br />

… Parameter not available for HYDROVAR Single drive<br />

Parameters which are available on all HYDROVAR drives are marked with the following symbol:<br />

G<br />

… “global” parameter (available on all HYDROVAR drives)<br />

NOTICE! All changes are saved automatically and will not be lost with the removal of<br />

power supply!<br />

00 00 MAIN MENU<br />

The 1st windows, REQUIRED VALUE [02] and EFFECTIVE REQUIRED VALUE [03], depend on parameter<br />

MODE [0105]. The differences within the windows in the various modes are shown below:<br />

a) Active MODE [0105] = <strong>Controller</strong> (Default setting)<br />

ITT XX.X Hz<br />

STOP X.XX PSI<br />

1st window display in <strong>Controller</strong> mode<br />

This window shows the current run status of the drive.<br />

ON Running Stop the HYDROVAR by pressing ▼<br />

STOP <strong>Manual</strong>ly stopped Start the HYDROVAR by pressing ▲<br />

OFF E-Stop (X3/7-8) is open To start the HYDROVAR close E-Stop or bridge terminal X3/7-8<br />

b) For Active MODE [0105] = Cascade Relay, Cascade Serial, or Cascade Synchron<br />

* ADR X PX XX.X Hz<br />

STOP X.XX PSI<br />

Display for cascade serial and cascade relay modes<br />

This window shows the drive status.<br />

* Indicates which HYDROVAR controls the system. The parameters are described further below:<br />

ADR X <strong>Pump</strong> address, (1, 2, 3.....8)<br />

Cascade relay mode: Indicates the number of pumps that are running<br />

P X (ex. P3 …. Master + 2 fixed speed pumps are running)<br />

Cascade serial/synchron mode: Indicates where the drive is in the existing sequence.<br />

37<br />