Programming<br />
1100 1100 SUBMENU SETUP<br />
1110<br />
1110 FACTORY SET<br />
USA<br />
Possible settings: EUROPE, USA<br />
Restores the HV to factory setting<br />
To restore the HYDROVAR to factory settings select Europe or USA.<br />
For reset press button until “DONE” appears.<br />
1120<br />
1120 PASSWORD 2<br />
0000<br />
Enter password by pressing ▲ or ▼<br />
The below mentioned parameters are available after entering the correct password!<br />
For more information, contact your local distributor!<br />
1125 1125 CLR ERRORS Clear error memory of selected unit<br />
UNIT X or on ALL units (Cascade Serial/Synchron)<br />
Possible settings: 1 – 8, ALL<br />
To clear the error memory either (1-8) for one specific unit or ALL for all units, can be selected.<br />
For reset press button till “RESET” appears.<br />
1130 1130 CLR MOTORH. Clear motor hours for selected unit<br />
UNIT X or on ALL units (Cascade Serial/Synchron)<br />
Possible settings: 1 – 8, ALL<br />
Set desired unit where the Motor Hours should be cleared (or ALL) and press button until “RESET”<br />
appears.<br />
1135<br />
1135 CLR OPERAT.<br />
Press 3 sec.<br />
Clear operation time<br />
The operation time indicates the total time the HYDROVAR is already connected to power supply. For reset<br />
the operation time of the current HYDROVAR press button till “RESET” appears.<br />