Programming<br />

Calculations of the new required value for multi pump applications:<br />

k ... number of active pumps (k >1)<br />

p = p set + (k-1)*[lift value – fall value]<br />

• Lift value = Fall value ⇒ Pressure constant independent of how many pumps are in operation<br />

• Lift value > Fall value ⇒ Pressure rises when assist pump switches on<br />

• Lift value < Fall value ⇒ Pressure falls when assist pump switches on<br />

The following 3 parameters are responsible for starting the assist pumps and to calculate the new required<br />

value.<br />

0505<br />

0505 ACT. VAL. INC.<br />

5 PSI<br />

Lift value<br />

Possible settings: 0.00 – to the pre selected sensor range<br />

0510 ACT. VAL. DEC.<br />

0510<br />

2 PSI<br />

Drop value<br />

Possible settings: 0.00– to the pre selected sensor range<br />

0515<br />

0515 ENABLE FRQ<br />

48.0 Hz<br />

Possible settings: 0.0 – 70.0 Hz<br />

Enable frequency for the next drive<br />

Sets the frequency for the next pump to turn on. If a pump in the system reaches this frequency and the<br />

system pressure drops below the REQUIRED VALUE [02] - ACTUAL VALUE DECREASE [0510], the next<br />

pump is started.<br />

0520<br />

0520 ENABLE DLY<br />

5 sec<br />

Possible settings: 0 – 100 sec<br />

Enable delay time (for cascade relay only!)<br />

Delay, in seconds, after the current pump reaches the enable frequency, before the next pump turns on.<br />

0525<br />

0525 SW DELAY<br />

5 sec<br />

Possible settings: 0 – 100 sec<br />

Switch delay (for cascade relay only!)<br />

Delay time between two switching actions of the fix speed pump. The parameter prevents the system<br />

repeated switching actions caused by varying demand.<br />