Programming<br />

0570<br />

0570 MSTPRIORITY<br />

ON<br />

Possible settings: ON - OFF<br />

Master priority (for cascade serial / synchron only!)<br />

This parameter determines the alternation order when Master and Basic Inverters are used within one<br />

system. In such a case you have to select if either the master or the Basic Inverters should be switched on<br />

first.<br />

ON - all Master Inverters in the system start (unless it is stopped manually or by a failure) before the first<br />

Basic Inverter runs.<br />

For example: Address 1-3.......Master Inverters<br />

Address 4-8……Basic Inverters<br />

Switching order: Adr 1 Adr 2 Adr 3 Adr 4 Adr 5 Adr 6 Adr 7 Adr 8<br />

Master Master Master Basic Basic Basic Basic Basic<br />

OFF - One master (which controls the overall system) is running. With rising consumption all Basic Inverters<br />

are turned on before other Masters run.<br />

Switching order: Adr 1 Adr 4 Adr 5 Adr 6 Adr 7 Adr 8 Adr 2 Adr 3<br />

Master Basic Basic Basic Basic Basic Master Master<br />

0600<br />

0605<br />

0600 SUBMENU<br />

ERRORS<br />

0605 MIN. THRESH.<br />

disabled<br />

Minimum threshold limit<br />

Possible settings: disabled - max. SENSOR RANGE<br />

• An adjusted value >0.00 has to be reached within the programmed DELAY TIME [0610]<br />

• If this value can’t be reached, the HYDROVAR stops with the failure message ”MIN. THRESHOLD ERROR”.<br />

• To disable the minimum threshold limit, press ▼ till “disabled” is shown on the display.<br />

0610<br />

0610 DELAY - TIME<br />

2 Sec<br />

Possible settings: 1 – 100 sec<br />

Minimum threshold limit delay time<br />

Delay time to switch-off the HYDROVAR if the actual value drops below the minimum threshold limit or a<br />

connected external low water protection at terminals X3/11-12 has been opened.<br />

Notice: The minimum threshold function is also active during start up of the pump! Therefore the delay<br />

time has to be set higher than the duration that is needed, to reach a value above the limit.<br />