Programming<br />
0415<br />
0415 SENSOR TYPE<br />
4 – 20mA<br />
Selection of the sensor type and input terminal<br />
Possible settings: - analog I 4-20mA - analog I 0-20mA - analog U 0-10V<br />
For choosing the correct sensor input.<br />
Sensor type: Terminals:<br />
- analog I 4-20mA The actual value is represented by a current X3/2 -> Sensor 1<br />
- analog I 0-20mA signal connected to following terminals: * X3/4 -> Sensor 2<br />
- analog U 0-10V The actual value is given from a voltage signal X3/6 -> Sensor 1<br />
connected to following terminals: * X3/5 -> Sensor 2<br />
* … Sensor 2 is not available for the Single Inverter configuration<br />
0420<br />
0420 SENS. RANGE<br />
20mA = 300 PSI<br />
Sensor range<br />
Possible settings: 0.00 – 10000<br />
Determines the end value (=20mA or 10V) of the connected sensor.<br />
The maximum sensor range -> 20mA = 100% of the sensor range.<br />
Example:<br />
300 PSI pressure sensor => 20mA = 300 PSI<br />
0425<br />
0425 SENS. CURVE<br />
linear<br />
Sensor curve<br />
Possible settings: linear, quadratic<br />
Internal calculation based on the actual value.<br />
Possible setting and its application:<br />
• Linear: Pressure control, differential pressure control, level, temperature and flow control (inductive or<br />
mechanical).<br />
• Quadratic: Flow control using an orifice plate together with a differential pressure sensor.<br />
0430<br />
0430 SENS 1 CAL 0<br />
0% = actual value<br />
Sensor 1 zero point calibration<br />
Possible settings: - 10% up to +10%<br />
This parameter is used to calibrate the minimum value of Sensor 1. After setting the dimension unit and<br />
the sensor range the zero point for this sensor can be adjusted. Adjustable range between -10 % and +10<br />
%.<br />
56