Programming<br />

0415<br />

0415 SENSOR TYPE<br />

4 – 20mA<br />

Selection of the sensor type and input terminal<br />

Possible settings: - analog I 4-20mA - analog I 0-20mA - analog U 0-10V<br />

For choosing the correct sensor input.<br />

Sensor type: Terminals:<br />

- analog I 4-20mA The actual value is represented by a current X3/2 -> Sensor 1<br />

- analog I 0-20mA signal connected to following terminals: * X3/4 -> Sensor 2<br />

- analog U 0-10V The actual value is given from a voltage signal X3/6 -> Sensor 1<br />

connected to following terminals: * X3/5 -> Sensor 2<br />

* … Sensor 2 is not available for the Single Inverter configuration<br />

0420<br />

0420 SENS. RANGE<br />

20mA = 300 PSI<br />

Sensor range<br />

Possible settings: 0.00 – 10000<br />

Determines the end value (=20mA or 10V) of the connected sensor.<br />

The maximum sensor range -> 20mA = 100% of the sensor range.<br />

Example:<br />

300 PSI pressure sensor => 20mA = 300 PSI<br />

0425<br />

0425 SENS. CURVE<br />

linear<br />

Sensor curve<br />

Possible settings: linear, quadratic<br />

Internal calculation based on the actual value.<br />

Possible setting and its application:<br />

• Linear: Pressure control, differential pressure control, level, temperature and flow control (inductive or<br />

mechanical).<br />

• Quadratic: Flow control using an orifice plate together with a differential pressure sensor.<br />

0430<br />

0430 SENS 1 CAL 0<br />

0% = actual value<br />

Sensor 1 zero point calibration<br />

Possible settings: - 10% up to +10%<br />

This parameter is used to calibrate the minimum value of Sensor 1. After setting the dimension unit and<br />

the sensor range the zero point for this sensor can be adjusted. Adjustable range between -10 % and +10<br />

%.<br />

56