Failure Messages<br />

LACK OF WATER<br />

ERROR 21<br />

• Incoming pressure or minimum level<br />

too low<br />

Low water contact • Bridge X3/11-12, if there is no ext.<br />

(X3/11-12) is opened low water protection<br />

(only active if motor is running) • Adjust Parameter DELAY TIME [0610]<br />

if the failure happens only for a<br />

short time<br />

Reset: • Automatically if low water contact (X3/11-12) is closed!<br />

Defined value of parameter • Check booster unit, adjust<br />

MIN. THRESHOLD MIN.THRESHOLD [0605] was parameter DELAY TIME [0610]<br />

ERROR 22 not reached during the • Parameter ERROR RESET [0615] set<br />

preselected DELAY-TIME [0610] to ON, to enable 5 restarts<br />

FAILURE SENSOR 1<br />

ACT. VAL. SENSOR 1<br />

ERROR 23<br />

FAILURE SENSOR 2<br />

ACT. VAL. SENSOR 2<br />

ERROR 24<br />

Sensor signal on terminals<br />

X3/2 ERROR<br />

Non-active sensor: WARNING<br />

Sensor signal on terminals<br />

X3/2 ERROR<br />

Non-active sensor: WARNING<br />

74<br />

• ACTUAL VALUE signal (pressure<br />

transducer) faulty<br />

• Poor connection<br />

• Sensor or cable fault<br />

• check configuration of the sensors<br />

in submenu SENSORS [0400]<br />

• ACTUAL VALUE signal (pressure<br />

transducer) faulty<br />

• Poor connection<br />

• Sensor or cable fault<br />

• check configuration of the sensors<br />

in submenu SENSORS [0400]<br />

• Check external analogue signal on<br />

SETPOINT 1 I