Programming<br />

0325<br />

0325 FRQ. LIFT<br />

30.0 Hz<br />

Possible settings: 0.0 Hz – 70.0 Hz<br />

Frequency limit for required lift value<br />

Control according to a system curve (increase of the set pressure, depending on the flow rate/speed to<br />

cover friction losses).<br />

The setting determines the output-frequency where the set pressure starts to be increased. The right<br />

setting should be equal to the frequency when the pump reaches the set pressure at zero flow (Can be<br />

determined by using the JOG MODE [0305]).<br />

0330<br />

0330 LIFT AMOUNT<br />

0.0 %<br />

Possible settings: 0.0 – 200.0%<br />

Lift amount for required lift value<br />

This value states how much the set value should be continually increased, till the maximum speed (maximum<br />

volume) is reached.<br />

Application Example:<br />

1) Enter the set pressure (see main menu<br />

parameter REQ. VAL [02]).<br />

2) Find out the frequency where set pressure<br />

is reached at zero demand (use<br />

JOG MODE [0305]) and set the value in<br />

parameter FREQU. LIFTING.<br />

3) Set desired lift at maximum speed in % of<br />

the set pressure in the parameter LIFT-<br />

AMOUNT [0330].<br />

A … set pressure<br />

B … window<br />

C … lift intensity in % of set pressure<br />