Failure Messages<br />

Error Probable Cause Measure<br />

• Check Parameter RAMP 1/2 [0215 /<br />

0220] (too short) and BOOST [0265]<br />

(too low)<br />

OVERLOAD Power limit of the HYDROVAR • Check motor connection, cable and<br />

ERROR 12 is exceeded power supply<br />

• <strong>Pump</strong> blocked<br />

• Motor turns in the wrong direction<br />

• MAX. FREQUENCY [0245] too high<br />

OVERVOLTAGE<br />

ERROR 13<br />

DC voltage too high<br />

• Parameter RAMP 2 [0220] too fast<br />

• Power supply too high<br />

• Voltage peaks too high (Solution: Line<br />

filters)<br />

INVERT. OVERHEAT Excessive temperature inside<br />

ERROR 14 the HYDROVAR<br />

THERMO MOT/EXT<br />

ERROR 15<br />

An external protective device<br />

connected to terminal X1/PTC<br />

has released (e.g. PTC which is<br />

connected has reached its<br />

release temperature).<br />

PHASELOSS One phase of the power supply<br />

ERROR 16 has been lost.<br />

73<br />

• Improper cooling<br />

• Contamination of the motor vents<br />

• Ambient temperature too high<br />

• Close X1/PTC if there is no external<br />

protective device connected.<br />

• Close external on/off switch if<br />

connected to these terminals.<br />

• For detailed information, see<br />

chapter 8.4.3.<br />

• Check power supply under full load.<br />

– Check if phase failure at the input.<br />

• Check circuit breakers<br />

• Visual inspection of points at the<br />

input terminals.<br />

• Supply voltage too low<br />

UNDERVOLTAGE DC voltage • Phase failure at the input<br />

• Asymmetry of the phase imbalance<br />

COMM LOST<br />

Reset:<br />

• Check if the addressing of Basic<br />

Inverter [DIP SW.] has been done<br />

The communication between correctly.<br />

the Power Unit and the control<br />

• Check if each unit has its own pump<br />

card is lost. address.<br />

• Check if the connection from<br />

control card to the power unit is<br />

made properly (ribbon cable).<br />

• Cut off power supply for > 60 seconds.<br />

• <strong>Manual</strong> reset by closing external ON/OFF (Terminals X3/7-8)<br />

• <strong>Manual</strong> reset by pressing and simultaneously for about 5 seconds<br />

• Auto-reset possible if ERROR-RESET [0615] is set to ON