Failure Messages<br />
Error Probable Cause Measure<br />
• Check Parameter RAMP 1/2 [0215 /<br />
0220] (too short) and BOOST [0265]<br />
(too low)<br />
OVERLOAD Power limit of the HYDROVAR • Check motor connection, cable and<br />
ERROR 12 is exceeded power supply<br />
• <strong>Pump</strong> blocked<br />
• Motor turns in the wrong direction<br />
• MAX. FREQUENCY [0245] too high<br />
OVERVOLTAGE<br />
ERROR 13<br />
DC voltage too high<br />
• Parameter RAMP 2 [0220] too fast<br />
• Power supply too high<br />
• Voltage peaks too high (Solution: Line<br />
filters)<br />
INVERT. OVERHEAT Excessive temperature inside<br />
ERROR 14 the HYDROVAR<br />
THERMO MOT/EXT<br />
ERROR 15<br />
An external protective device<br />
connected to terminal X1/PTC<br />
has released (e.g. PTC which is<br />
connected has reached its<br />
release temperature).<br />
PHASELOSS One phase of the power supply<br />
ERROR 16 has been lost.<br />
73<br />
• Improper cooling<br />
• Contamination of the motor vents<br />
• Ambient temperature too high<br />
• Close X1/PTC if there is no external<br />
protective device connected.<br />
• Close external on/off switch if<br />
connected to these terminals.<br />
• For detailed information, see<br />
chapter 8.4.3.<br />
• Check power supply under full load.<br />
– Check if phase failure at the input.<br />
• Check circuit breakers<br />
• Visual inspection of points at the<br />
input terminals.<br />
• Supply voltage too low<br />
UNDERVOLTAGE DC voltage • Phase failure at the input<br />
• Asymmetry of the phase imbalance<br />
COMM LOST<br />
Reset:<br />
• Check if the addressing of Basic<br />
Inverter [DIP SW.] has been done<br />
The communication between correctly.<br />
the Power Unit and the control<br />
• Check if each unit has its own pump<br />
card is lost. address.<br />
• Check if the connection from<br />
control card to the power unit is<br />
made properly (ribbon cable).<br />
• Cut off power supply for > 60 seconds.<br />
• <strong>Manual</strong> reset by closing external ON/OFF (Terminals X3/7-8)<br />
• <strong>Manual</strong> reset by pressing and simultaneously for about 5 seconds<br />
• Auto-reset possible if ERROR-RESET [0615] is set to ON