Programming<br />

0800<br />

0805<br />

Config. Explanation of status Action if status=YES<br />

Power HYDROVAR is connected to power supply<br />

Running Motor is running<br />

63<br />

Relay 1: X5/ 1-3 closed<br />

Relay 2: X5/ 4-6 closed<br />

Relay 1: X5/ 1-3 closed<br />

Relay 2: X5/ 4-6 closed<br />

Errors An error is indicated on the HYDROVAR Relay 1: X5/ 1-2 closed<br />

(incl. power failure) Relay 2: X5/ 4-5 closed<br />

Warnings A warning is indicated on the HYDROVAR Relay 1: X5/ 1-2 closed<br />

Relay 2: X5/ 4-5 closed<br />

StandBy<br />

Errorreset<br />

<strong>Pump</strong> is manually turned off or E-stop activated, Relay 1: X5/ 1-3 closed<br />

no error/warning is indicated and HYDROVAR doesn’t run Relay 2: X5/ 4-6 closed<br />

If Parameter ERRORRESET [0615] is activated and a Relay 1: X5/ 1-3 closed<br />

Warning occurs 5 times -> Error -> Relay 2: X5/ 4-6 closed<br />

Error of<br />

A failure is indicated at least on one Basic drive<br />

Relay 1: X5/ 1-2 closed<br />

Basics Relay 2: X5/ 4-5 closed<br />

Warnings A warning is indicated on the Master or Relay 1: X5/ 1-2 closed<br />

+ Basics at least one Basic drive Relay 2: X5/ 4-5 closed<br />

0800 SUBMENU<br />

REQUIRED VALUES<br />

0805 C.REQ.VAL 1<br />

digital<br />

Configuration required value 1<br />

Possible settings: - digital - analog U 0-10V<br />

- analog I 0-20mA - analog I 4-20mA<br />

Digital<br />

analog U=0 – 10V<br />

The internal required value 1 is used.<br />

Setting in the main menu in Parameter 02 or parameter [0820].<br />

The required value 1 is determined by the value of a voltage signal<br />

(0 – 10V) connected to terminals X3/13- X3/14 (GND).<br />

The required value 1 is determined by the value of a current signal<br />

analog I=0 – 20mA (4 – 20mA or 0 – 20mA) connected to terminals X3/18- X3/17<br />

(GND).<br />

Notice: If the incoming current signal drops below 4mA (4-20mA<br />

analog I=4 – 20mA setting), a warning message is shown on the display. If the failure is<br />

still active after 20 seconds, an error message will be shown.<br />

The changeover between the 1st and the 2nd required value can be done either internally or externally via<br />

the digital inputs. With the following parameters the source of the required values and the change over<br />

can be configured.<br />