Programming<br />
0800<br />
0805<br />
Config. Explanation of status Action if status=YES<br />
Power HYDROVAR is connected to power supply<br />
Running Motor is running<br />
63<br />
Relay 1: X5/ 1-3 closed<br />
Relay 2: X5/ 4-6 closed<br />
Relay 1: X5/ 1-3 closed<br />
Relay 2: X5/ 4-6 closed<br />
Errors An error is indicated on the HYDROVAR Relay 1: X5/ 1-2 closed<br />
(incl. power failure) Relay 2: X5/ 4-5 closed<br />
Warnings A warning is indicated on the HYDROVAR Relay 1: X5/ 1-2 closed<br />
Relay 2: X5/ 4-5 closed<br />
StandBy<br />
Errorreset<br />
<strong>Pump</strong> is manually turned off or E-stop activated, Relay 1: X5/ 1-3 closed<br />
no error/warning is indicated and HYDROVAR doesn’t run Relay 2: X5/ 4-6 closed<br />
If Parameter ERRORRESET [0615] is activated and a Relay 1: X5/ 1-3 closed<br />
Warning occurs 5 times -> Error -> Relay 2: X5/ 4-6 closed<br />
Error of<br />
A failure is indicated at least on one Basic drive<br />
Relay 1: X5/ 1-2 closed<br />
Basics Relay 2: X5/ 4-5 closed<br />
Warnings A warning is indicated on the Master or Relay 1: X5/ 1-2 closed<br />
+ Basics at least one Basic drive Relay 2: X5/ 4-5 closed<br />
0800 SUBMENU<br />
REQUIRED VALUES<br />
0805 C.REQ.VAL 1<br />
digital<br />
Configuration required value 1<br />
Possible settings: - digital - analog U 0-10V<br />
- analog I 0-20mA - analog I 4-20mA<br />
Digital<br />
analog U=0 – 10V<br />
The internal required value 1 is used.<br />
Setting in the main menu in Parameter 02 or parameter [0820].<br />
The required value 1 is determined by the value of a voltage signal<br />
(0 – 10V) connected to terminals X3/13- X3/14 (GND).<br />
The required value 1 is determined by the value of a current signal<br />
analog I=0 – 20mA (4 – 20mA or 0 – 20mA) connected to terminals X3/18- X3/17<br />
(GND).<br />
Notice: If the incoming current signal drops below 4mA (4-20mA<br />
analog I=4 – 20mA setting), a warning message is shown on the display. If the failure is<br />
still active after 20 seconds, an error message will be shown.<br />
The changeover between the 1st and the 2nd required value can be done either internally or externally via<br />
the digital inputs. With the following parameters the source of the required values and the change over<br />
can be configured.<br />
S