Programming<br />
0115<br />
0115 LOCK FUNCT.<br />
OFF<br />
Possible settings: ON - OFF<br />
Change with ▲ or ▼<br />
OFF: All parameters in the MAIN menu (only) can be changed without entering the password.<br />
ON: If the LOCK FUNCTION is activated, no changes can be made in any parameter without first entering<br />
the password. The HYDROVAR can be started and stopped with the up/down arrows. To change the set<br />
value, the LOCK FUNCTION must be set to OFF.<br />
0120<br />
0120 DISP. CONTR.<br />
75 %<br />
Display Contrast<br />
Possible settings: 10 – 100%<br />
Can be adjusted between 10 - 100%, to improve the display.<br />
0125<br />
0125 DISP. BRIGHT<br />
100 %<br />
Display Brightness<br />
Possible settings: 10 – 100%<br />
The backlight intensity of the display can be adjusted.<br />
0200 0200 SUBMENU CONF<br />
INVERTER<br />
0202<br />
0202 SOFTWARE<br />
HV V01.3<br />
Software version of the control board<br />
0202 0202 SW RD V01.0 Software version of the Remote display (RD) (not available) and<br />
HV V01.3 the control board (HV)<br />
0203<br />
0203 SET VER.INV<br />
sel:01 act:01<br />
Possible settings: 00 - 02<br />
Activate additional settings. Contact factory to use.<br />
Activates skip frequency parameter and current limit functions. These functions are not commonly used,<br />
and may have undesirable effects. They should only be used to solve application problems in the field.<br />
Press and hold the right arrow for 5 seconds to activate the function, and "Done" is displayed.The following<br />
parameters [0285], [0286], [0290] and [0291] are added to the parameter list.)<br />
Setting 00: all units with production date prior 05/2008<br />
Setting 01: Basic 2 - 5 HP (on control board software V01.3)<br />
Setting 02: Basic 7.5 - 15 HP (on control board software V01.3)<br />
47<br />