Programming<br />

0255<br />

0255 CONF. FMIN f -> 0<br />

Possible settings: f->0 or f->f min<br />

<strong>Operation</strong> at minimum frequency<br />

f->0: After reaching the required pressure with no demand the frequency drops to the selected MINIMUM<br />

FREQUENCY [0250] and the HYDROVAR will continue to run for the selected F MIN TIME [0260]. After this<br />

time the HYDROVAR will stop automatically.<br />

f->f min: The pump will never stop automatically. The frequency will only drop down to the selected MINI-<br />

MUM FREQUENCY [0250]. To stop the pump the external ON/OFF (E-stop) must be opened or the ▼ (Stop)<br />

button must be pressed.<br />

Applications: circulation systems<br />

0260<br />

Caution: The setting f->f min can overheat the pump if there is no flow through the pump.<br />

Use when there is a bypass line for circulation pumps!<br />

0260 FMIN TIME<br />

0 s<br />

Possible settings: 0 – 100 sec<br />

Delay time before shut off below MIN. FREQ.<br />

After running below MIN. FREQ.for this selected time, the pump will stop if parameter CONFIG. FMIN<br />

[0255] is set to f -> 0.<br />

0265<br />

0265 BOOST<br />

5 %<br />

Motor starting voltage in % of connected supply voltage<br />

Possible settings: 0 – 25% of the input voltage<br />

This parameter determines the characteristics of the voltage/frequency curve. In particular, it refers to the<br />

voltage increase during startup as a percentage of the nominal voltage. This setting should be kept as low<br />

as possible to protect the motor from thermal overload at lower frequencies. If the boost is set too low, a<br />

failure (OVERLOAD) may occur because the starting current is too high.<br />

0270<br />

0270 KNEE FRQ.<br />

60.0 Hz<br />

Knee frequency<br />

Possible settings: 30.0 – 90.0 Hz<br />

This parameter determines the frequency at which the HYDROVAR generates its maximum output voltage<br />

(value of the connected input voltage). For standard applications this frequency should be set to MAX.<br />

FRQ. [0245] (Default Setting 60Hz).<br />

Caution<br />

This parameter should rarely be adjusted! Incorrect setting can cause an overload<br />

error and damage to the motor. Contact factory before changing.<br />