Programming<br />

0530<br />

0530 DISABLE FRQ<br />

30 Hz<br />

Possible settings: 0.0 – 120.0 Hz<br />

Disable frequency (for cascade relay only!)<br />

The frequency to switch off the fixed speed pumps in cascade relay-mode.<br />

If the Master Inverter goes below that frequency for longer than the pre-selected DISABLE DLY [0535] and<br />

the system pressure is higher than the EFFECTIVE REQ. VALUE [03] (REQUIRED VALUE [02] + ACTUAL VAL.<br />

INC [0505]), the first assist pump stops.<br />

0535<br />

0535 DISABLE DLY<br />

5 sec<br />

Possible settings: 0 – 100 sec<br />

Disable delay time (for cascade relay only!)<br />

Delay time before switching off the assist pumps in cascade relay mode.<br />

0540<br />

0540 DROP FRQ<br />

42 Hz<br />

Possible settings: 0.0 – 70.0 Hz<br />

Drop frequency (for cascade relay only!)<br />

This parameter is used to prevent the system from pressure hammers. Before a following pump starts up,<br />

the Master Inverter will drop to the selected frequency. If the DROP FREQUENCY is reached, the follow-uppump<br />

gets released and the Master Inverter will continue with normal operation.<br />

0545<br />

0545 OVERVALUE<br />

OFF<br />

Overvalue (for cascade relay only!)<br />

Possible settings: OFF – pre selected sensor range<br />

If this selected value is reached, an immediate shut-off of the fixed speed pumps is executed.<br />

E.g. REQUIRED VALUE [02]: 70 PSI<br />

OVERVALUE [0545]: 100 PSI<br />

If three pumps are running (1 Master Inverter + 2 fixed speed pumps) and a system pressure of 100 PSI is<br />

reached, one after another assist pump is switched off.<br />

This parameter prevents the system against overpressure in case the HYDROVAR has been parameterized<br />

incorrectly.<br />

0550<br />

0550 OVERVAL DLY<br />

0 sec<br />

Possible settings: 0.0 – 10.0 sec<br />

Overvalue delay (for cascade relay only!)<br />

Delay time to switch off an assist pump in case the actual value exceeds the OVERVALUE [0545] limit.<br />