Programming<br />

0291<br />

0291 CURR. LIMIT<br />

100 %<br />

Current limit<br />

Possible settings: 10.0 - 100 %<br />

Previous parameters [0285] - [0291] are limited for power ratings starting from 7.5kW with production<br />

date 05/08 and control board software V01.3 → otherwise they are not visible and therefore not active.<br />

0300<br />

0305<br />

0300 SUBMENU<br />

REGULATION<br />

0305 JOG 0.0Hz<br />

X.XX PSI<br />

Both the current output frequency and actual value are shown.<br />

• By pressing ▲ or ▼ in this menu, the internal controller of the HYDROVAR is deactivated and it changes<br />

to manual mode.<br />

• Using the ▲ and ▼ buttons any constant speed can be set without further control to achieve the set<br />

point!<br />

• If this value becomes 0.00 Hz the HYDROVAR stops.<br />

• As soon as the window is left by pressing or , the HYDROVAR returns to the selected mode.<br />

0310<br />

0310 WINDOW<br />

5%<br />

Hysteresis Window<br />

Possible settings: 0 – 100% of required value<br />

• Determines the width of the set point hysteresis window.<br />

• For steep pump-curves and closed loop systems ~20-30%.<br />

0315<br />

0315 HYSTERESIS<br />

80%<br />

Possible settings: 0 – 100%<br />

Hysteresis for ramp switching<br />

• Determines the percentage of the hysteresis window, at which the ramps change from slow to fast.<br />

• For an accurate control (without automatic shut-off) ~99%, e.g. constant flow control.<br />

0320<br />

0320 REG. MODE<br />

normal<br />

Regulation mode<br />

Possible settings: normal, inverse<br />

Normal: Speed is increased with falling actual value signals. (e.g.: control at constant output pressure)<br />

Inverse: Speed is reduced with falling actual value signal. (e.g.: control at constant suction pressure or at<br />

constant level on the suction side)<br />

53<br />