Programming<br />
0275 POWER REDUCT.<br />
0275<br />
OFF<br />
Reduction of the maximum output current<br />
Possible settings: OFF, 85%, 75%, 50%<br />
If a motor with lower nominal power is used, the maximum output current should be adjusted accordingly.<br />
The reduction of the maximum output current also affects the overload-detection!<br />
HV Horsepower<br />
0280<br />
52<br />
Output current [A]<br />
OFF = 100% 85% 75% 50%<br />
230V, 2 HP 7 5.95 5.25 3.5<br />
230V, 3 HP 10 8.50 7.50 5.00<br />
230V, 3 HP 5.7 4.85 4.28 2.85<br />
230V, 5 HP 7.3 6.21 5.48 3.65<br />
230V, 7.5 HP 13.5 11.48 10.13 6.75<br />
230V, 10 HP 17 14.45 12.75 8.5<br />
230V, 15 HP 23 19.55 17.25 11.5<br />
0280 SEL. SW. FRQ.<br />
Auto<br />
Selection of the switching frequency<br />
Possible settings: Auto, 8 kHz, 4 kHz<br />
• Auto (default setting)<br />
In standard operation the HYDROVAR works with a switching frequency of 8 kHz in order to reduce the<br />
noise level. At rising temperature inside the HYDROVAR the switching frequency is decreased to 4 kHz<br />
automatically.<br />
• 8 kHz - Selection with lowest noise level, but without decrease at rising temperature.<br />
• 4 kHz - Reduce the temperature in the HYDROVAR<br />
0285<br />
0285 SKIPFRQ CTR<br />
0.0 Hz<br />
Possible settings: f min - f max<br />
0286<br />
0286 SKIPFRQ RNG<br />
0.0 Hz<br />
Skip frequency start point<br />
Skip frequency range<br />
Possible settings: 0.0 – 5.0 Hz<br />
0290<br />
0290 CURR. LIMIT<br />
OFF<br />
Possible settings: OFF - ON<br />
Current limit functionality<br />