Programming Flow Chart<br />
Section 12 (continued)<br />
62 JOG Hz<br />
50 PSI<br />
61 PASSWORD<br />
0000<br />
60 SUBMENU<br />
SETTINGS<br />
100 SUBMENU<br />
BASIC SETTINGS<br />
125 DISP. BRIGHT<br />
100 %<br />
120 DISP. CONTR.<br />
75 %<br />
115 LOCK FUNCT.<br />
0066<br />
110 SET PASSW.<br />
0066<br />
106 PUMP ADDR<br />
1<br />
105 MODE<br />
<strong>Controller</strong><br />
100 SUBMENU<br />
BASIC SETTINGS<br />
220 RAMP 2<br />
4 sec<br />
215 RAMP 1<br />
4 sec<br />
210 INVERTER<br />
ALL<br />
205 MAX. UNITS<br />
6<br />
203 SET VER INV<br />
sel. 01 act. 01<br />
202 SOFTWARE<br />
HV V01.3<br />
200 SUBMENU<br />
CONF INVERTER<br />
250 MIN. FREQ<br />
20 Hz<br />
245 MAX. FREQ<br />
60 Hz<br />
240 RAMP FMIN D<br />
2 sec<br />
235 RAMP FMIN A<br />
2 sec<br />
230 RAMP 4<br />
70 sec<br />
225 RAMP 3<br />
70 sec<br />
280 SEL.SW.FRQ.<br />
Auto<br />
275 POWER RED.<br />
OFF<br />
270 KNEE FREQ.<br />
60 Hz<br />
265 BOOST<br />
5 %<br />
260 FMIN TIME<br />
0 sec<br />
255 CONF. FMIN<br />
F > 0<br />
200 SUBMENU<br />
CONF INVERTER<br />
291 CURR. LIMIT<br />
100 %<br />
290 CURR. LIMIT<br />
OFF<br />
286 SKIPFRQ RNG<br />
60 Hz<br />
285 SKIPFRQ CTR<br />
0.0 Hz<br />
78<br />
300 SUBMENU<br />
REGULATION<br />
330 LIFT AMOUNT<br />
0.0 %<br />
325 FRQ. LIFT<br />
30.0 Hz<br />
320 REG. MODE<br />
normal<br />
315 HYSTERESIS<br />
80 %<br />
310 WINDOW<br />
10 %<br />
305 JOG Hz<br />
50 PSI<br />
300 SUBMENU<br />
REGULATION<br />
430 SENS1 CAL 0<br />
0 % = x,xx PSI<br />
425 SENS. CURVE<br />
linear<br />
420 SENS. RANGE<br />
300 PSI<br />
415 SENSOR TYPE<br />
analog I 4-20mA<br />
410 CONF SENSOR<br />
Sensor 1<br />
405 DIMENS. UNIT<br />
PSI<br />
400 SUBMENU<br />
SENSOR<br />
400 SUBMENU<br />
SENSOR<br />
445 SENS2 CAL X<br />
0 % = xx,xx PSI<br />
440 SENS2 CAL 0<br />
0 % = x,xx PSI<br />
435 SENS1 CAL X<br />
0 % = xx,xx PSI<br />
530 DISABLE FRQ<br />
30.0 Hz<br />
525 SWITCH DLY<br />
2 sec<br />
520 ENABLE DLY<br />
5 sec<br />
515 ENABLE FREQ<br />
48 Hz<br />
510 ACT.VAL.DEC<br />
2 PSI<br />
505 ACT.VAL.INC<br />
5 PSI<br />
500 SUBMENU<br />
SEQUENCE CNTR<br />
560 SYNCH.LIM.<br />
0.0 Hz<br />
555 SWITCH INTV<br />
24 hours<br />
550 OVERVAL DLY<br />
0 sec<br />
545 OVERVALUE<br />
disabled<br />
540 DROP FREQ<br />
42.0 Hz<br />
535 DISABLE DLY<br />
5 sec<br />
500 SUBMENU<br />
SEQUENCE CNTR<br />
570 MSTPRIORITY<br />
ON<br />
565 SYNCH.WIN.<br />
2 Hz