Programming<br />
This pre-selected required value is active in all modes except Actuator if parameter C.REQ.VAL.1 [0805]<br />
or C.REQ.VAL.2 [0810] is set to digital, and parameter SW REQ.VAL. [0815] is set to setpoint 1/2 or the<br />
REQUIRED VALUE 1/2 is selected via digital input.<br />
This pre-selected required value could also be taken over in the main menu with parameter REQUIRED<br />
VAL. [02] if the current required value is active.<br />
0830<br />
0830 ACTUAT.FRQ 1<br />
XX.X Hz<br />
Required frequency 1 for actuator<br />
Possible settings: 0.0 – MAX. FREQ. [0245]<br />
0835<br />
0835 ACTUAT.FRQ 2<br />
XX.X Hz<br />
Required frequency 2 for actuator<br />
Possible settings: 0.0 – MAX. FREQ. [0245]<br />
Set the frequency with either ▲ or ▼.<br />
The selected frequency in this parameter is only active in the actuator mode if parameter C.REQ.VAL.1<br />
[0805] or C.REQ.VAL.2 [0810] is set to digital, and parameter SW REQ.VAL [0815] is set to setpoint 1/2 or<br />
the ACTUATOR FREQUENCY 1/2 is selected via digital input.<br />
0900 0900 SUBMENU OFFSET<br />
The Offset function allows for a change in setpoint based on a separate process parameter, (ex., flow rate).<br />
Use of this function is not recommended. Contact factory for further information.<br />
0905<br />
0905 OFFS. INPUT<br />
OFF<br />
Selection of the Offset Input<br />
Possible settings: OFF analog U1 0-10V analog U2 0-10V<br />
analog I1 0-20mA / 4-20mA analog I2 0-20mA / 4-20mA<br />
0907 OFFSET RANGE<br />
0907<br />
100<br />
Possible settings: 0 – 10000<br />
Representation of the sensor range<br />
The Offset Range can be set to a number between 0 and 10000. Its value depends on the maximum range<br />
of the connected offset sensor.<br />
E.g.: 300 PSI sensor can be set as range: 300; 3000; 30000<br />
The higher the offset range the higher the resolution on the signal input.<br />
65<br />