System Design<br />

Section 2<br />

The following diagrams show typical single and multi-pump systems using the HYDROVAR Variable Speed<br />

Drive. Connect directly to water supply. Use of a low suction pressure switch is recommended.<br />

General<br />

NOTE<br />

Systems MUST be designed by qualified technicians only and meet all applicable state and local<br />

code requirements.<br />

CAUTION<br />

Hazardous<br />

Pressure<br />

Single <strong>Pump</strong> Layout Multi-<strong>Pump</strong> Layout<br />

6 7 7<br />

1<br />

4 5 4<br />

8<br />

2<br />

4<br />

9<br />

(1) pump with HYDROVAR (4) gate valve (7) pressure gauge<br />

(2) diaphragm tank (5) check valve or ball valve (8) pressure transducer<br />

(3) fusible disconnect (6) low suction pressure switch (9) pressure relief valve<br />

Note<br />

All plumbing work must be performed by a qualified technician. Always follow all local, state and<br />

provincial codes.<br />

A proper installation requires a pressure relief valve, a ¼" female N.P.T. threaded fitting for the pressure sensor,<br />

and properly sized pipe. Piping should be no smaller than the pump discharge and/or suction connections.<br />

Piping should be kept as short as possible. Avoid the use of unnecessary fittings to minimize friction losses.<br />

Some pump and motor combinations supplied with this system can create dangerous pressure.<br />

Select pipe and fittings according to your pipe suppliers’ recommendation. Consult local codes for<br />

piping requirements in your area.<br />

All joints must be airtight. Use Teflon tape or another type of pipe sealant to seal threaded connections. Use<br />

caution when using thread sealant as any excess that gets inside the pipe may plug the pressure sensor.<br />

Galvanized fittings or pipe should never be connected directly to the stainless steel discharge head or casing as<br />

galvanic corrosion may occur. Barb type connectors should always be double clamped.<br />

5<br />

3<br />

1<br />

6 7 4 5 4<br />

8<br />

1<br />

4 5 4<br />

8<br />

1<br />

4 5 4<br />

8<br />

7<br />

2<br />

9<br />

4