Programming<br />
0810<br />
0810 C.REQ.VAL 2<br />
OFF<br />
Configuration required value 2<br />
Possible settings: - OFF - digital - analog U 0-10V<br />
- analog I 0-20mA - analog I 4-20mA<br />
0815<br />
OFF Required value 2 is not used.<br />
digital<br />
analog U 0 – 10V<br />
The internal required value 2 is used.<br />
Setting in the main menu in Parameter 02 or Parameter [0825].<br />
The required value 2 is determined by the value of a voltage<br />
signal (0 – 10V) connected to terminals X3/15- X3/16 (GND).<br />
The required value 2 is determined by the value of a current<br />
analog I 0 – 20mA signal (4 – 20mA or 0 – 20mA) connected to terminals<br />
X3/23- X3/22 (GND).<br />
Notice: If the incoming current signal falls below 4mA (4-20mA<br />
analog I 4 – 20mA setting), a warning message is shown on the display. If the failure is<br />
still active after 20 seconds, an error message will be shown.<br />
0815 SW REQ. VAL<br />
Setpoint 1<br />
Switching between required value 1 and 2<br />
Possible settings: - Setpoint 1 - Setpoint 2<br />
- Switch Dig 1 - Switch Dig 2<br />
- Switch Dig 3 - Switch Dig 4<br />
Setpoint 1: Only required value 1 is active (No switching possible)<br />
Setpoint 2: Only required value 2 is active (No switching possible)<br />
Switch Dig 1: <strong>Manual</strong> switching by closing digital input 1 (X3/9-10)<br />
Switch Dig 2: <strong>Manual</strong> switching by closing digital input 2 (X3/6-10)<br />
Switch Dig 3: <strong>Manual</strong> switching by closing digital input 3 (X3/5-10)<br />
Switch Dig 4: <strong>Manual</strong> switching by closing digital input 4 (X3/15-16)<br />
0820<br />
0820 REQ.VAL.1<br />
XX.X PSI<br />
Required value 1 (digital)<br />
Possible settings: 0.0 – to the pre selected sensor range<br />
0825<br />
0825 REQ.VAL.2<br />
XX.X PSI<br />
Required value 2 (digital)<br />
Possible settings: 0.0 – to the pre selected sensor range<br />
Set the desired required value with either ▲ or ▼.<br />
64<br />