Failure Messages<br />
Reset:<br />
To reset the CODE ERROR and the OVERCURRENT ERROR, cut power<br />
supply for > 60 seconds.<br />
To reset all other errors open/close the START/STOP_PTC input (X1/PTC) on<br />
the power unit.<br />
If the Basic Inverter is used in combination with a Master Inverter, each failure can be indicated on the<br />
Master Inverter too and will be saved in the failure memory including date and time when the failure appeared.<br />
Indication on the Master Inverter: For detailed failure information on the<br />
ERR. Basic Addr. X specific unit, SUBMENU STATUS [20] has to be entered and the affected<br />
device has to be selected with it’s pump address!<br />
If a Master Inverter is used in such a system, the errors which occurred on the Basic Inverter can be reset by<br />
the Master without interfering with the operation of the other HYDROVAR units in the system (also valid for<br />
automatic Error-reset).<br />
10.2 Master / Single Inverter<br />
Each error is shown on the display in plain text and saved in the error memory.<br />
The errors can be reset automatically (depending on the setting in parameter ERROR-RESET [0615]) or<br />
manually in following ways:<br />
• cutting the power supply for > 60 seconds<br />
• pressing and simultaneously for about 5 seconds<br />
• open and close the External ON/OFF (Terminals X3/7-8)<br />
No error-message on the display<br />
Error Probable Cause Measure<br />
no AUTOSTART after Parameter AUTOSTART [08] is Check parameter AUTOSTART [08]<br />
power failure set to “OFF”<br />
No operation when system Pressure higher than the start Check parameter START VALUE [04]<br />
pressure < set pressure value or REGULATION MODE and/or REGULATION MODE [0320]<br />
has been changed to INVERSE.<br />
Error-message on the display<br />
Error Probable Cause Measure<br />
OVERCURRENT<br />
ERROR 11<br />
Reset:<br />
• check connection-terminals of the<br />
Current rise at the output HYDROVAR<br />
• check the connection-terminal of<br />
too high<br />
the motor and the motor-cable<br />
• check the windings of the motor<br />
• The power supply for >60 seconds.<br />
• Automatic Error-reset not possible for this failure!<br />
72