Failure Messages<br />

Reset:<br />

To reset the CODE ERROR and the OVERCURRENT ERROR, cut power<br />

supply for > 60 seconds.<br />

To reset all other errors open/close the START/STOP_PTC input (X1/PTC) on<br />

the power unit.<br />

If the Basic Inverter is used in combination with a Master Inverter, each failure can be indicated on the<br />

Master Inverter too and will be saved in the failure memory including date and time when the failure appeared.<br />

Indication on the Master Inverter: For detailed failure information on the<br />

ERR. Basic Addr. X specific unit, SUBMENU STATUS [20] has to be entered and the affected<br />

device has to be selected with it’s pump address!<br />

If a Master Inverter is used in such a system, the errors which occurred on the Basic Inverter can be reset by<br />

the Master without interfering with the operation of the other HYDROVAR units in the system (also valid for<br />

automatic Error-reset).<br />

10.2 Master / Single Inverter<br />

Each error is shown on the display in plain text and saved in the error memory.<br />

The errors can be reset automatically (depending on the setting in parameter ERROR-RESET [0615]) or<br />

manually in following ways:<br />

• cutting the power supply for > 60 seconds<br />

• pressing and simultaneously for about 5 seconds<br />

• open and close the External ON/OFF (Terminals X3/7-8)<br />

No error-message on the display<br />

Error Probable Cause Measure<br />

no AUTOSTART after Parameter AUTOSTART [08] is Check parameter AUTOSTART [08]<br />

power failure set to “OFF”<br />

No operation when system Pressure higher than the start Check parameter START VALUE [04]<br />

pressure < set pressure value or REGULATION MODE and/or REGULATION MODE [0320]<br />

has been changed to INVERSE.<br />

Error-message on the display<br />

Error Probable Cause Measure<br />

OVERCURRENT<br />

ERROR 11<br />

Reset:<br />

• check connection-terminals of the<br />

Current rise at the output HYDROVAR<br />

• check the connection-terminal of<br />

too high<br />

the motor and the motor-cable<br />

• check the windings of the motor<br />

• The power supply for >60 seconds.<br />

• Automatic Error-reset not possible for this failure!<br />

72