Powering Europe - European Wind Energy Association
Powering Europe - European Wind Energy Association
Powering Europe - European Wind Energy Association
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
2.2 An overview of the present<br />
grid code requirements for wind<br />
power<br />
Essential requirements<br />
Technical grid code requirements and related documents<br />
vary from one electricity system to another.<br />
However, for simplicity, the typical requirements for<br />
generators can be grouped as follows:<br />
• Tolerance - that is, the range of conditions on the<br />
electricity system for which wind power plants must<br />
continue to operate<br />
• Control of reactive power: this often includes requirements<br />
to contribute to the control of voltage<br />
in the network<br />
• Control of active power and frequency response<br />
• Protective devices<br />
• Power quality<br />
• Visibility of the power plant in the network<br />
It is important to note that these requirements are<br />
often specified at the Point of Connection (POC) of<br />
the wind power plant to the electricity network. In<br />
this case, the requirements are placed on the wind<br />
power plant. To achieve them the requirements for<br />
wind turbines may have to be different. Often wind<br />
turbine manufacturers will only specify the performance<br />
of their wind turbines, not the entire wind power<br />
plant. EWEA recommends that for transparency and<br />
inter-comparability, all grid codes should specify the<br />
requirements to apply at POC. It is also possible to<br />
meet some of the requirements by providing additional<br />
equipment separate from wind turbines. This is noted<br />
below where relevant.<br />
tolerance<br />
The wind power plant must continue to operate between<br />
minimum and maximum limits of voltage. Usually<br />
this is stated as steady-state quantities, though a<br />
wider range may apply for a limited duration.<br />
chApTEr 2 <strong>Wind</strong>generationandwindplants:theessentials<br />
The wind power plant must also continue to operate<br />
between minimum and maximum limits of frequency.<br />
Usually there is a range which is continuously applied,<br />
and several further more extreme short-term ranges.<br />
Early generation wind turbines (type A) 13 are generally<br />
not capable of meeting wider operational frequency<br />
ranges as stipulated in several grid codes. However,<br />
the operation of a wind turbine in a wider frequency<br />
range is not really a complicated task as it mainly involves<br />
the thermal overloading of equipment, which<br />
has short thermal time-constants, in particular by using<br />
power electronic components. A possible solution<br />
for short-term overload capability consists of oversizing<br />
the converters, which in general can be done<br />
at reasonable cost. Increased operating temperature<br />
may also result in a reduced insulation lifetime. However,<br />
since operation at deviating frequency occurs<br />
rarely, the effect is negligible and can be reduced by<br />
limiting power output at the extremities of the frequency<br />
range. Therefore – in general - wind turbines can be<br />
made to operate in wider frequency ranges.<br />
In systems with relatively high wind penetration, it is<br />
common that wind power plants are required to continue<br />
to operate during severe system disturbances,<br />
during which the voltage can drop to very low levels for<br />
very short periods. This is termed fault ride-through<br />
(FRT) or low voltage ride-through. A decade back, the<br />
TSOs required all wind turbines to disconnect during<br />
faults. Today they demand that wind turbines stay on<br />
the grid through these disturbances. Faults are inevitable<br />
on any electrical system and can be due to natural<br />
causes (e.g. lightning), equipment failure or third<br />
party damage. With relatively low transmission circuit<br />
impedances, such fault conditions can cause a large<br />
transient voltage depression across wide network areas.<br />
Conventional large synchronous generators are –<br />
in general - expected to trip only if a permanent fault<br />
occurs in the circuit to which they are directly connected<br />
14 . Other generators that are connected to adjacent<br />
healthy circuits should remain connected and stable<br />
after the faulty circuits are disconnected, otherwise<br />
too much generation will be lost in addition to that<br />
13 <strong>Wind</strong> turbine electrical concept types as previously defined.<br />
14 The actual fulfilment of the FrT requirement is not always the case with large conventional generators such as some new ccGT’s in<br />
<strong>Europe</strong> and nuclear power plants in the USA.<br />
57