G 70 ECM/Sensor Troubleshooting<br />

5.2 Checking Outgoing Power From the ECM<br />

Prerequisites Fully-charged (12+ Volts) battery<br />

At least 9.8 VDC incoming power to ECM on red wires #18 and #53<br />

Procedure Follow the procedure below to check the outgoing power from the ECM.<br />

1. Open the control panel and locate the ECM.<br />

2. Place the START/RUN switch in the ON position.<br />

3. Check the voltage between pin 1 plug 2 (yellow wire #63) and ground.<br />

Is at least 9.8 VDC measured?<br />

Yes ____ No ____ Your reading<br />

Continue. The ECM has failed.<br />

Call <strong>Wacker</strong> <strong>Neuson</strong> Service.<br />

4. Check the voltage between pin 2 plug 2 (violet wire #64) and ground.<br />

Is at least 9.8 VDC measured?<br />

Yes ____ No ____<br />

Outgoing power from the ECM is OK. The ECM has failed.<br />

Outgoing power from the ECM has now been checked.<br />

wc_tx000956gb.fm 41