G 70 Troubleshooting Engine Start System<br />
7 Troubleshooting Engine Start System<br />
7.1 Checking Fuses<br />
Prerequisites Battery voltage measuring 11–13 VDC<br />
Procedure Follow the procedure below to check the fuses.<br />
1. Locate the 10A and 30A fuses.<br />
2. Check the condition of the 30A fuse. (Note: If the ECM display is blank when the<br />
START/RUN switch is in the ON position, the 30A fuse is most likely blown.)<br />
Is the fuse OK?<br />
Yes____ No____<br />
Continue. Replace the fuse with one of the same size and rating.<br />
Check the function of the main circuit breaker. The shunt of<br />
the main circuit breaker is most likely the cause of a fuse failure.<br />
See Section 7.7 Checking the Main Circuit Breaker.<br />
3. Check the condition of the 10A fuse.<br />
Is the fuse OK?<br />
Yes____ No____<br />
Continue. Replace the fuse with one of the same size and rating.<br />
This procedure continues on the next page.<br />