G 70 Output Voltage Troubleshooting<br />

8.8 Checking the AVR Sensing/Power Wires<br />

Prerequisites <strong>Generator</strong> shut down<br />

Procedure Follow the procedure below to check the AVR sensing/power wires.<br />

1. Open the large hinged panel and locate the Engine Control Module (ECM) and<br />

the Automatic Voltage Regulator (AVR).<br />

2. Disconnect the 4-pin connector (it has 3 wires) from the ECM.<br />

3. Remove the green and black wires from the AVR.<br />

4. Measure the resistance across the green and black wires.<br />

Is 0.2–1.0 Ohms measured?<br />

Yes ____ No ____ Your reading<br />

Continue. Remove the vent cover from the generator and<br />

check the generator for damage.<br />

5. Measure the resistance between the green wire and the ground lug. Also check<br />

between the black wire and the ground lug.<br />

Is 0.2–1.0 Ohms measured?<br />

Yes ____ No ____ Your reading<br />

Continue. Remove the vent cover from the generator and<br />

check the generator for damage.<br />

6. Remove the bus bar between the neutral lug and the ground lug.<br />

7. Measure the continuity between the green wire and the ground lug. Also check<br />

between the black wire and the ground lug.<br />

Does each wire measure “OPEN” or “OL” to the ground lug?<br />

Yes ____ No ____ Your reading<br />

The sensing wires<br />

are OK.<br />

This procedure continues on the next page.<br />

wc_tx000958gb.fm 75<br />

Remove the vent cover from the generator and<br />

check the generator for damage.