Repair Manual Mobile Generator - Wacker Neuson
Repair Manual Mobile Generator - Wacker Neuson
Repair Manual Mobile Generator - Wacker Neuson
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
G 70 ECM/Sensor Troubleshooting<br />
Continued from the previous page.<br />
7. Open the control panel and locate the VOLTS ADJ pot on the ECM.<br />
WARNING<br />
Electric shock hazard. High voltage exists at the cooling fins of the Automatic Voltage<br />
Regulator (AVR) when the engine is running. Electric shock can cause severe<br />
injury or death.<br />
Do not touch the AVR when the engine is running.<br />
8. Adjust the VOLTS ADJ pot until the ECM reads the same as the voltage measured<br />
at the lugs.<br />
9. Re-install the key to the door switch and close the control panel.<br />
The ECM voltage has now been calibrated.<br />
wc_tx000956gb.fm 45