G 70 Output Voltage Troubleshooting<br />
Continued from the previous page.<br />
5. Measure the voltage between the two yellow wires and ground.<br />
Is at least 9.8 VDC measured?<br />
Yes ____ No ____<br />
The main circuit Check condition/connection of yellow wire between the main<br />
breaker has failed; circuit breaker and the terminal strip. There must be more than<br />
replace it. 9.8 VDC between the wire and ground. When voltage exists,<br />
repeat step 4.<br />
6. Place the key into the lug door switch.<br />
7. With the main circuit breaker in the ON position, check for continuity (continuity<br />
equals 0.0–1.0 Ohms) between L1 of the main circuit breaker and Lug 1. Also<br />
check between L2 and Lug 2, and L3 and Lug 3.<br />
Is there continuity for each check?<br />
Yes ____ No ____ Your reading<br />
Continue. The main circuit breaker has<br />
failed; replace it. ____; _____; _____<br />
8. With the main circuit breaker in the OFF position, check for continuity between<br />
L1 of the main circuit breaker and Lug 1. Also check between L2 and Lug 2, and<br />
L3 and Lug 3.<br />
Is there continuity for any of the checks?<br />
9. Reconnect the yellow (Y) wires and lug door key.<br />
The main circuit breaker has now been checked. Continue with Section 8.5<br />
Checking the Voltage Adjusting Rheostat.<br />
wc_tx000958gb.fm 71<br />
Yes ____ No ____<br />
The main circuit breaker has failed;<br />
replace it.<br />
The main circuit breaker is functioning<br />
properly.