APPENDIX CC<br />

Electrical Safety Audit Checklist (cont’d)<br />

Outdoor lights must be a minimum of 5 feet from pool<br />

horizontally or greater than 12 feet above the water level of<br />

the pool.<br />

GFCI protection for lights greater than 5 feet and less than<br />

10 feet from the pool.<br />

Indoor lights that are 7.5 feet above the water are allowed<br />

if they are enclosed and GFCI protected.<br />

Pool light fixture ground wires must be unspliced, except at<br />

the terminals.<br />

Bond together pool shell, metal equipment for pumps, pool<br />

covers, underwater light forming shelf, and all metal less<br />

than 5 feet from the pool.<br />

Bonding wire must be a minimum solid 8 American Wire<br />

Gauge (AWG) copper.<br />

The top of an underwater fixture must be a minimum of 18<br />

inches below pool water surface level.<br />

Any junction box must be a minimum of 8 inches above the<br />

surface water level and 4 inches above the deck level.<br />

Junction boxes must be a minimum of 4 feet from edge of<br />

the pool.<br />

Cord-and-Plug connections for spas and hot tubs with a<br />

cord less than 15 feet in length are permitted providing<br />

they are GFCI protected.<br />

Cord-and-plug connected equipment flexible cord should<br />

not exceed 3 feet or 900 mm in length.<br />

There must be at least one 125-volt, 15 or 20 ampere<br />

receptacle, on a general purpose branch circuit located not<br />

less than 6 feet from and not exceeding 10 feet from the<br />

inside wall of the spa or hot tub.<br />

The use of portable electrical devices, such as announcing<br />

systems and radios within the reach of bathers must not be<br />

allowed.<br />

Name of Facility Inspector: ____________________________________________<br />

Signature of Facility Inspector: _________________________________________<br />

Date of Inspection: ____________________________________________________<br />

© 2014 <strong>National</strong> Swimming Pool Foundation® Page 239