S-Schutz<br />

Easy Choice<br />

L1 L2 L3 N PE<br />

Arrangement I Arrangement II Arrangement III<br />

SPD Type 3<br />

(Surge arrester)<br />

SPD Type 3<br />

(Surge arrester)<br />

SPD Type 3<br />

(Surge arrester)<br />

DEHNflex<br />

Socket Outlet<br />

Cable length ≥ 5 m<br />

1 x DSA 230 LA Part No. 924 370<br />

for cable ducts<br />

1 x DFL M 255 Part No. 924 396<br />

for flush-mounted systems<br />

1 x STC 230 Part No. 924 350<br />

for existing socket outlets<br />

16 A<br />

125 A 1<br />

125 A 1<br />

DEHNguard<br />

L1<br />

DG MOD 275<br />

DEHNguard<br />

L2<br />

DG MOD 275<br />

1 x DG M TNS 275 Part No. 952 400<br />

315 A 1<br />

DEHNguard<br />

L3<br />

DG MOD 275<br />

9<br />

SPD Type 2<br />

(Surge arrester)<br />

Cable length ≥ 15 m<br />

SPD Type 1<br />

(Lightning current arrester)<br />

L1 L1’ L2 L2’ L3 L3’<br />

DEHNbloc DB 3 255 H<br />

DEHNguard<br />

N<br />

PE<br />

DG MOD 275<br />

N‘/PEN<br />

N/PEN<br />

DEHNguard<br />

L1<br />

DG MOD 275<br />

DEHNguard<br />

L2<br />

DG MOD 275<br />

with remote signalling contact:<br />

1 x DG M TNS 275 FM Part No. 952 405<br />

315 A 1<br />

L/N<br />

DEHNbloc<br />

DB M 1 255 FM<br />

N/PE(N)<br />

L/N<br />

DEHNguard<br />

DEHNbloc<br />

L3<br />

DG MOD 275<br />

9<br />

SPD Type 2<br />

(Surge arrester)<br />

DB M 1 255 FM<br />

N/PE(N)<br />

DEHNguard<br />

N<br />

PE<br />

L/N<br />

DG MOD 275<br />

DEHNbloc<br />

DB M 1 255 FM<br />

N/PE(N)<br />

fault indication<br />

DEHNbloc ® M<br />

Coordinated with DEHNguard ®<br />

without additional cable length.<br />

SPD Type 1<br />

(Coordinated lightning<br />

current arrester)<br />

fault indication<br />

315 A 1<br />

DEHNventil ®<br />

Directly coordinated with<br />

Red/Line SPDs Type 2 and 3<br />

without additional cable length.<br />

For series connection please see also page 18<br />

SPD Type 1<br />

(Combined lightning current<br />

and surge arrester)<br />

L1 L1‘ L2 L2‘<br />

DEHNventil<br />

DV MOD 255<br />

DEHNventil<br />

DV MOD 255<br />

L3 L3‘<br />

9<br />

DEHNventil<br />

PEN<br />

DV MOD 255<br />

Main Distribution Board Sub-distribution Board<br />

MEB<br />

1 x DB 3 255<br />

alt. 3 x DB 1 255 H<br />

1 x MVS 1 6<br />

Part No. 900 120<br />

Part No. 900 222<br />

Part No. 900 815<br />

3 x DB M 1 255 FM Part No. 961 125<br />

1 x MVS 1 6 Part No. 900 815<br />

alt. 3 x DB M 1 255 Part No. 961 120<br />

1 x MVS 1 6 Part No. 900 815<br />

1 x DV M TNC 255 Part No. 951 300<br />

alt. 1 x DV M TNC 255 FM Part No. 951 305<br />

also available as<br />

1 x DV M TNS 255 Part No. 951 400<br />

alt. 1 x DV M TNS 255 FM Part No. 951 405<br />

1) Only required, if no fuse of the same or a lower nominal value is provided in the upstream power supply.<br />

L1 L2 L3<br />

PEN<br />

TN system: Office building – Separation of the PEN conductor in the main distribution board<br />

www.dehn.de 15