Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Pluggable DIN Rail Mounted SPDs<br />
BLITZDUCTOR ® XT LifeCheck ® Modules<br />
BXT ML2 BE S 5 – BE S 48<br />
1<br />
1´<br />
2<br />
2´<br />
45<br />
protected<br />
12 51<br />
(2/3 mods.)<br />
3<br />
4<br />
3´<br />
4´<br />
Dimension drawing BXT ML2 BE<br />
Basic circuit diagram BXT ML2 BE<br />
Space-saving combined lightning current and surge arrester module with LifeCheck feature for protecting<br />
two single lines with common reference potential as well as unbalanced interfaces, with<br />
direct or indirect shield earthing. If LifeCheck detects thermal or electrical overload, the arrester has<br />
to be replaced. This status is indicated contactlessly by the DEHNrecord LC / MCM reader.<br />
• LifeCheck SPD monitoring function<br />
• Optimal protection of two single lines<br />
and line shield<br />
• For use in conformity with the lightning<br />
protection zones concept at the boundaries<br />
from 0 A – 2 and higher<br />
920 220<br />
BXT ML2 BE S 5<br />
920 222<br />
BXT ML2 BE S 12<br />
920 224<br />
BXT ML2 BE S 24<br />
BXT 920 226 ML2 BE S 5<br />
920 BXT 220 ML2 BE S 36<br />
Kombiableiter-Modul 920 225<br />
für 2 EinzeladernBLITZDUCTOR XT mit LifeCheck<br />
BXT ML2 BE S 12 48<br />
920 222<br />
Kombiableiter-Modul für 2 EinzeladernBLITZDUCTOR XT mit LifeCheck<br />
BXT ML2 BE S 24<br />
920 224<br />
Kombiableiter-Modul für 2 EinzeladernBLITZDUCTOR XT mit LifeCheck<br />
BXT ML2 BE S 36<br />
920 226<br />
Kombiableiter-Modul für 2 Einzeladern<br />
BLITZDUCTOR<br />
XT mit LifeCheck<br />
BXT ML2 BE S 48<br />
920 225<br />
Kombiableiter-Modul für 2 EinzeladernBLITZDUCTOR XT mit LifeCheck<br />
Type BXT ML2 BE S 5 BXT ML2 BE S 12 BXT ML2 BE S 24 BXT ML2 BE S 36 BXT ML2 BE S 48<br />
Part No. 920 220 920 222 920 224 920 226 + 920 225<br />
SPD class M M M M M<br />
SPD monitoring system LifeCheck LifeCheck LifeCheck LifeCheck LifeCheck<br />
Nominal voltage (U N ) 5 V 12 V 24 V 36 V 48 V<br />
Max. continuous operating d.c. voltage (U C ) 6.0 V 15 V 33 V 45 V 54 V<br />
Max. continuous operating a.c. voltage (U C ) 4.2 V 10.6 V 23.3 V 31 V 38.1 V<br />
Nominal current at 45°C (I L ) 1.0 A 0.75 A 0.75 A 1.8 A 0.75 A<br />
D1 Total lightning impulse current (10/350 μs) (I imp ) 9 kA 9 kA 9 kA 9 kA 9 kA<br />
D1 Lightning impulse current (10/350 μs) per line (I imp ) 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA<br />
C2 Total nominal discharge current (8/20 μs) (I n ) 20 kA 20 kA 20 kA 20 kA 20 kA<br />
C2 Nominal discharge current (8/20 μs) per line (I n ) 10 kA 10 kA 10 kA 10 kA 10 kA<br />
Voltage protection level line-line for I imp D1 (U p ) ≤ 29 V ≤ 50 V ≤ 102 V –– ≤ 160 V<br />
Voltage protection level line-PG for I imp D1 (U p ) ≤ 27 V ≤ 37 V ≤ 66 V ≤ 85 V ≤ 95 V<br />
Voltage protection level line-line at 1 kV/μs C3 (U p ) ≤ 18 V ≤ 38 V ≤ 90 V ≤ 112 V ≤ 140 V<br />
Voltage protection level line-PG at 1 kV/μs C3 (U p ) ≤ 9 V ≤ 19 V ≤ 45 V ≤ 56 V ≤ 70 V<br />
Series impedance per line 1.0 ohm 1.8 ohms 1.8 ohms 0.43 ohms 1.8 ohms<br />
Cut-off frequency line-PG (f G ) 1.0 MHz 2.7 MHz 6.8 MHz 3.8 MHz 8.7 MHz<br />
Capacitance line-line (C) ≤ 2.7 nF ≤ 1.0 nF ≤ 0.5 nF ≤ 0.8 nF ≤ 0.35 nF<br />
Capacitance line-PG (C) ≤ 5.4 nF ≤ 2.0 nF ≤ 1.0 nF ≤ 1.6 nF ≤ 0.7 nF<br />
Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C<br />
Degree of protection<br />
(with plugged-in protection module) IP 20 IP 20 IP 20 IP 20 IP 20<br />
Pluggable into base part base part base part base part base part<br />
Earthing via base part base part base part base part base part<br />
Enclosure material polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6<br />
Colour yellow yellow yellow yellow yellow<br />
Test standards<br />
IEC 61643-21 / EN 61643-21, UL 497B<br />
SIL classification SIL2 / SIL3 * ) SIL2 / SIL3 * ) SIL2 / SIL3 * ) –– SIL2 / SIL3 * )<br />
ATEX approvals DEKRA 11ATEX0089 X: DEKRA 11ATEX0089 X: DEKRA 11ATEX0089 X: DEKRA 11ATEX0089 X:<br />
II 3 G Ex nA IIC T4 Gc II 3 G Ex nA IIC T4 Gc II 3 G Ex nA IIC T4 Gc –– II 3 G Ex nA IIC T4 Gc<br />
IECEx approvals DEK 11.0032X: DEK 11.0032X: DEK 11.0032X: DEK 11.0032X:<br />
Ex nA IIC T4 Gc Ex nA IIC T4 Gc Ex nA IIC T4 Gc –– Ex nA IIC T4 Gc<br />
Approvals CSA, GOST, VdS CSA, GOST, VdS CSA, GOST, VdS UL, VdS CSA, UL, GOST, VdS<br />
*) For more detailed information, please refer to www.dehn.de/en/sil/ and page 210<br />
Accessories for BLITZDUCTOR ® XT LifeCheck ® Modules<br />
Labelling system BA1-BA15<br />
2x165 adhesive labels for labelling<br />
DRC MCM XT monitoring devices<br />
with their bus address.<br />
Type BS BA1 BA15 BXT<br />
Part No. 920 398<br />
Colour<br />
white<br />
Earthing module<br />
For direct earthing of lines connected<br />
to the BLITZDUCTOR XT<br />
base part.<br />
Type<br />
BXT M4 E<br />
Part No 920 308<br />
Colour<br />
grey<br />
Test / Disconnection module<br />
Module for testing lines, plugs into<br />
BLITZDUCTOR XT base parts<br />
Type<br />
BXT M4 T<br />
Part No 920 309<br />
Colour<br />
grey<br />
For ”Accessories for BLITZDUCTOR XT LifeCheck modules“, please also refer to pages 188/206/207/208/368/370.<br />
www.dehn.de<br />
199