Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Coordinated Type 1 Lightning Current Arresters<br />
DEHNbloc ® M<br />
DEHNbloc M 1 ... FM<br />
30<br />
L/N<br />
L/N<br />
L'/N'<br />
90<br />
N/PE(N)<br />
36 7<br />
(2 mods.)<br />
43.5<br />
66<br />
45<br />
12<br />
11<br />
14<br />
9<br />
11<br />
15.3<br />
N/PE(N)<br />
961 115<br />
DB M 1 150 FM<br />
961 125<br />
DB M 1 255 FM<br />
961 135<br />
DB M 1 320 FM<br />
DB M 1 150 FM<br />
961 115<br />
Koordinierter Blitzstromableiter Typ 1 DEHNbloc M mit hoher<br />
Folgestrombegrenzung<br />
DB M 1 255 FM<br />
961 125<br />
Koordinierter Blitzstromableiter Typ 1 DEHNbloc M mit hoher<br />
Folgestrombegrenzung<br />
DB M 1 320 FM<br />
961 135<br />
Koordinierter Blitzstromableiter Typ 1 DEHNbloc M mit hoher<br />
Folgestrombegrenzun<br />
Dimension drawing DB M 1 ... FM<br />
Basic circuit diagram DB M 1 ... FM<br />
Coordinated modular single-pole lightning current arrester with high follow current limitation; with<br />
remote signalling contact for monitoring system (floating changeover contact)<br />
• Coordinated spark-gap-based lightning<br />
current arrester consisting of a base<br />
part and plug-in protection module<br />
• Maximum system availability due to<br />
RADAX Flow follow current limitation<br />
• Directly coordinated with DEHNguard<br />
surge protective devices without additional<br />
cable length<br />
Type DB M 1 150 FM DB M 1 255 FM DB M 1 320 FM<br />
Part No. 961 115 961 125 961 135<br />
SPD according to EN 61643-11 Type 1 Type 1 Type 1<br />
SPD according to IEC 61643-1/-11 Class I Class I Class I<br />
Max. continuous operating a.c. voltage (U C ) 150 V 255 V 320 V<br />
Lightning impulse current (10/350 μs) (I imp ) 35 kA 50 kA 25 kA<br />
Specific energy (W/R) 306.25 kJ/ohms 625.00 kJ/ohms 156.25 kJ/ohms<br />
Nominal discharge current (8/20 μs) (I n ) 35 kA 50 kA 25 kA<br />
Voltage protection level (U P ) ≤ 1.5 kV ≤ 2.5 kV ≤ 2.5 kV<br />
Follow current extinguishing capability a.c. (I fi ) 50 kA rms 50 kA rms 50 kA rms<br />
Follow current limitation/Selectivity<br />
no tripping of a 32 A gL/gG fuse up to 50 kA rms (prosp.)<br />
Response time (t A ) ≤ 100 ns ≤ 100 ns ≤ 100 ns<br />
Max. backup fuse (L) up to I K = 50 kA rms (t a ≤ 0.2 s) 500 A gL/gG 500 A gL/gG 315 A gL/gG<br />
Max. backup fuse (L) up to I K = 50 kA rms (t a ≤ 5 s) 315 A gL/gG 315 A gL/gG 315 A gL/gG<br />
Max. backup fuse (L) for I K > 50 kA rms 200 A gL/gG 200 A gL/gG 200 A gL/gG<br />
Max. backup fuse (L-L') 125 A gL/gG 125 A gL/gG 125 A gL/gG<br />
Temporary overvoltage (TOV) (U T ) 200 V / 5 sec. 440 V / 5 sec. 440 V / 5 sec.<br />
TOV characteristics withstand withstand withstand<br />
Operating temperature range (parallel connection) (T UP ) -40°C...+80°C -40°C...+80°C -40°C...+80°C<br />
Operating temperature range (series connection) (T US ) -40°C...+60°C -40°C...+60°C -40°C...+60°C<br />
Operating state/fault indication green / red green / red green / red<br />
Number of ports 1 1 1<br />
Cross-sectional area (L/N, L'/N', N/PE (N)) (min.) 10 mm 2 solid/flexible 10 mm 2 solid/flexible 10 mm 2 solid/flexible<br />
Cross-sectional area (L/N, N/PE(N)) (max.) 50 mm 2 stranded/35 mm 2 flexible 50 mm 2 stranded/35 mm 2 flexible 50 mm 2 stranded/35 mm 2 flexible<br />
Cross-sectional area (L'/N') (max.) 35 mm 2 stranded/25 mm 2 flexible 35 mm 2 stranded/25 mm 2 flexible 35 mm 2 stranded/25 mm 2 flexible<br />
For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715<br />
Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0<br />
Place of installation indoor installation indoor installation indoor installation<br />
Degree of protection IP 20 IP 20 IP 20<br />
Capacity 2 modules, DIN 43880 2 modules, DIN 43880 2 modules, DIN 43880<br />
Approvals UL, CSA VDE, KEMA, UL UL, CSA<br />
Type of remote signalling contact changeover contact changeover contact changeover contact<br />
a.c. switching capacity 250 V/0.5 A 250 V/0.5 A 250 V/0.5 A<br />
d.c. switching capacity<br />
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A 250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A<br />
Cross-sectional area for remote signalling terminals max. 1.5 mm 2 solid/flexible max. 1.5 mm 2 solid/flexible max. 1.5 mm 2 solid/flexible<br />
Lightn. Curr. Arr. Type 1<br />
Accessory for DEHNbloc ® M<br />
DB M Spark-Gap-Based Protection Module<br />
Spark-gap-based protection module<br />
Type DB M MOD ... 150 255 320<br />
Part No. 961 001 961 002 961 003<br />
Max. continuous<br />
operating a.c. voltage (U C ) 150 V 255 V 320 V<br />
www.dehn.de<br />
51