Pluggable DIN Rail Mounted SPDs<br />
BLITZDUCTOR ® XT LifeCheck ® Modules<br />
BXT ML4 BD 5 – BD 180<br />
1<br />
1´<br />
2<br />
2´<br />
45<br />
protected<br />
12 51<br />
(2/3 mods.)<br />
3<br />
4<br />
3´<br />
4´<br />
Dimension drawing BXT ML4 BD<br />
Basic circuit diagram BXT ML4 BD<br />
Space-saving combined lightning current and surge arrester module with LifeCheck feature for protecting<br />
two pairs of unearthed balanced interfaces. If LifeCheck detects thermal or electrical overload,<br />
the arrester has to be replaced. This status is indicated contactlessly by the DEHNrecord LC /<br />
MCM reader.<br />
• LifeCheck SPD monitoring function<br />
• Optimal protection of two single pairs<br />
• For installation in conformity with the<br />
lightning protection zones concept at<br />
the boundaries from 0 A – 2 and higher<br />
920 340<br />
BXT ML4 BD 5<br />
920 342<br />
BXT ML4 BD 12<br />
920 344<br />
BXT ML4 BD 24<br />
BXT 920 345 ML4 BD 5<br />
920 BXT 340 ML4 BD 48<br />
Kombiableiter-Modul 920 346<br />
für 2 DoppeladernBLITZDUCTOR XT mit LifeCheck<br />
BXT ML4 BD 12 60<br />
920 342 347<br />
Kombiableiter-Modul BXT ML4 BD 180 für 2 DoppeladernBLITZDUCTOR XT mit LifeCheck<br />
BXT ML4 BD 24<br />
920 344<br />
Kombiableiter-Modul für 2 DoppeladernBLITZDUCTOR XT mit LifeCheck<br />
BXT ML4 BD 48<br />
920 345<br />
Kombiableiter-Modul für 2 DoppeladernBLITZDUCTOR XT mit LifeCheck<br />
BXT ML4 BD 60<br />
920 346<br />
Kombiableiter-Modul für 2 DoppeladernBLITZDUCTOR XT mit LifeCheck<br />
BXT ML4 BD 180<br />
920 347<br />
Kombiableiter-Modul für 2 DoppeladernBLITZDUCTOR XT mit LifeCheck<br />
Type BXT ML4 ... BD 5 BD 12 BD 24 BD 48 BD 60 BD 180<br />
Part No. 920 340 920 342 920 344 920 345 920 346 920 347<br />
SPD class M M M M M L<br />
SPD monitoring system LifeCheck LifeCheck LifeCheck LifeCheck LifeCheck LifeCheck<br />
Nominal voltage (U N ) 5 V 12 V 24 V 48 V 60 V 180 V<br />
Max. continuous operating d.c. voltage (U C ) 6.0 V 15 V 33 V 54 V 70 V 180 V<br />
Max. continuous operating a.c. voltage (U C ) 4.2 V 10.6 V 23.3 V 38.1 V 49.5 V 127 V<br />
Nominal current at 45°C (I L ) 1.0 A 1.0 A 1.0 A 1.0 A 1.0 A 0.75 A<br />
D1 Total lightning impulse current (10/350 μs) (I imp ) 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA<br />
D1 Lightning impulse current (10/350 μs) per line (I imp ) 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA<br />
C2 Total nominal discharge current (8/20 μs) (I n ) 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA<br />
C2 Nominal discharge current (8/20 μs) per line (I n ) 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA<br />
Voltage protection level line-line for I imp D1 (U p ) ≤ 25 V ≤ 26 V ≤ 52 V ≤ 80 V ≤ 110 V ≤ 270 V<br />
Voltage protection level line-PG for I imp D1 (U p ) ≤ 550 V ≤ 550 V ≤ 550 V ≤ 550 V ≤ 550 V ≤ 550 V<br />
Voltage protection level line-line at 1 kV/μs C3 (U p ) ≤ 9 V ≤ 19 V ≤ 45 V ≤ 70 V ≤ 90 V ≤ 250 V<br />
Voltage protection level line-PG at 1 kV/μs C3 (U p ) ≤ 550 V ≤ 550 V ≤ 550 V ≤ 550 V ≤ 550 V ≤ 550 V<br />
Series impedance per line 1.0 ohm 1.0 ohm 1.0 ohm 1.0 ohm 1.0 ohm 1.8 ohms<br />
Cut-off frequency line-line (f G ) 1.0 MHz 2.8 MHz 7.8 MHz 8.7 MHz 11.0 MHz 25.0 MHz<br />
Capacitance line-line (C) ≤ 5.4 nF ≤ 2.0 nF ≤ 1.0 nF ≤ 0.7 nF ≤ 500 pF ≤ 240 pF<br />
Capacitance line-PG (C) ≤ 16 pF ≤ 16 pF ≤ 16 pF ≤ 16 pF ≤ 16 pF ≤ 16 pF<br />
Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C<br />
Degree of protection<br />
(with plugged-in protection module) IP 20 IP 20 IP 20 IP 20 IP 20 IP 20<br />
Pluggable into base part base part base part base part base part base part<br />
Earthing via base part base part base part base part base part base part<br />
Enclosure material polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6<br />
Colour yellow yellow yellow yellow yellow yellow<br />
Test standards<br />
IEC 61643-21 / EN 61643-21, UL 497B<br />
SIL classification SIL2 / SIL3 * )<br />
ATEX approvals<br />
DEKRA 11ATEX0089 X: II 3 G Ex nA IIC T4 Gc<br />
IECEx approvals<br />
DEK 11.0032X: Ex nA IIC T4 Gc<br />
Approvals<br />
CSA, UL, VdS, GOST<br />
*) For more detailed information, please refer to www.dehn.de/en/sil/ and page 210<br />
Accessories for BLITZDUCTOR ® XT LifeCheck ® Modules<br />
Labelling system BA1-BA15<br />
2x165 adhesive labels for labelling<br />
DRC MCM XT monitoring devices<br />
with their bus address.<br />
Type BS BA1 BA15 BXT<br />
Part No. 920 398<br />
Colour<br />
white<br />
Earthing module<br />
For direct earthing of lines connected<br />
to the BLITZDUCTOR XT<br />
base part.<br />
Type<br />
BXT M4 E<br />
Part No 920 308<br />
Colour<br />
grey<br />
Test / Disconnection module<br />
Module for testing lines, plugs into<br />
BLITZDUCTOR XT base parts<br />
Type<br />
BXT M4 T<br />
Part No 920 309<br />
Colour<br />
grey<br />
For ”Accessories for BLITZDUCTOR XT LifeCheck modules“, please also refer to pages 188/206/207/208/368/370.<br />
www.dehn.de<br />
191