BLITZDUCTOR ® XT LifeCheck ® Modules<br />

Pluggable DIN Rail Mounted SPDs<br />

1<br />

1´<br />

BXT ML2 MY E 110<br />

+<br />

2<br />

2´<br />

45<br />

12 51<br />

(2/3 mods.)<br />

9<br />

3<br />

4<br />

protected<br />

3´<br />

4´<br />

Dimension drawing BXT ML2 MY E<br />

Basic circuit diagram BXT ML2 MY E<br />

Space-saving surge arrester module with LifeCheck feature for protecting two pairs of stranded signal<br />

interfaces. If LifeCheck detects thermal or electrical overload, the arrester has to be replaced.<br />

This status is indicated contactlessly by the DEHNrecord LC / MCM reader.<br />

Presumably available in the second quarter 2012<br />

• LifeCheck SPD monitoring<br />

• Distinctive “Y“ circuit<br />

• For installation in conformity with the<br />

lightning protection concept at the<br />

boundaries from 0 B – 2.<br />

920 288<br />

BXT ML2 MY E 110<br />

BXT ML2 MY E 110<br />

920 288<br />

Überspannungsableiter-Modul BLITZDUCTOR XT mit "Y"-<br />

Schaltung<br />

Type BXT ML2 MY E 110<br />

Part No. 920 288<br />

SPD class<br />

U<br />

SPD monitoring system<br />

LifeCheck<br />

Nominal voltage (U N )<br />

110 V<br />

Max. continuous operating d.c. voltage line-line (U C )<br />

170 V<br />

Max. continuous operating d.c. voltage line-PG (U C )<br />

85 V<br />

Max. continuous operating a.c. voltage line-line (U C )<br />

120 V<br />

Max. continuous operating a.c. voltage line-PG (U C )<br />

60 V<br />

Nominal current at 80°C (I L )<br />

3.0 A<br />

D1 Total lightning impulse current (10/350 μs) (I imp )<br />

0.6 kA<br />

D1 Lightning impulse current (10/350 μs) per line (I imp )<br />

0.3 kA<br />

C2 Total nominal discharge current (8/20 μs) (I n )<br />

5 kA<br />

C2 Nominal discharge current (8/20 μs) per line (I n )<br />

2.5 kA<br />

Voltage protection level line-line at 1 kV/μs C3 (U p )<br />

≤ 300 V<br />

Voltage protection level line-PG at 1 kV/μs C3 (U p )<br />

≤ 700 V<br />

Series impedance per line<br />

0 ohms<br />

Cut-off frequency line-line (f G )<br />

4.5 MHz<br />

Cut-off frequency line-line (100 ohms) (f G )<br />

2.2 MHz<br />

Capacitance line-line (C)<br />

≤ 1.5 nF<br />

Capacitance line-PG (C)<br />

≤ 25 pF<br />

Operating temperature range<br />

-40°C...+80°C<br />

Degree of protection (with plugged-in protection module) IP 20<br />

Pluggable into<br />

base part<br />

Earthing via<br />

base part<br />

Enclosure material polyamide PA 6.6<br />

Colour<br />

yellow<br />

Test standards IEC 61643-21 / EN 61643-21<br />

*) For more detailed information, please refer to www.dehn.de/en/sil/ and page 210<br />

Accessories for BLITZDUCTOR ® XT LifeCheck ® Modules<br />

Labelling system BA1-BA15<br />

2x165 adhesive labels for labelling<br />

DRC MCM XT monitoring devices<br />

with their bus address.<br />

Type BS BA1 BA15 BXT<br />

Part No. 920 398<br />

Colour<br />

white<br />

Earthing module<br />

For direct earthing of lines connected<br />

to the BLITZDUCTOR XT<br />

base part.<br />

Type<br />

BXT M4 E<br />

Part No 920 308<br />

Colour<br />

grey<br />

Test / Disconnection module<br />

Module for testing lines, plugs into<br />

BLITZDUCTOR XT base parts<br />

Type<br />

BXT M4 T<br />

Part No 920 309<br />

Colour<br />

grey<br />

For ”Accessories for BLITZDUCTOR XT LifeCheck modules“, please also refer to pages 188/206/207/208/368/370.<br />