DEHNrapid ® LSA<br />

Lightning current / surge arrester<br />

SPDs for LSA Technology<br />

1 2 3 4 5 6 7 8 9 0<br />

With an appropriate earthing frame, the fine limiting DEHNrapid LSA single-pair<br />

surge arresters can be plugged directly into the DRL plug-in SPD<br />

block or optionally into LSA disconnection blocks. The decoupling impedances<br />

integrated in the protective plugs allow energy coordination with<br />

the DRL plug-in SPD block irrespective of the cable length. The single-pair<br />

plug also allows partial equipment of LSA disconnection blocks and protective<br />

plugs with different circuits or nominal voltages can be plugged<br />

into one block.<br />

DRL protective plugs with earthing frame<br />

DRL combined lightning current and<br />

surge arrester<br />

The assembled unit of plug-in<br />

SPD block, earthing frame and<br />

protective plug (combined lightning<br />

current and surge arrester)<br />

can be removed and plugged in<br />

as a complete unit. The combined<br />

lightning current and<br />

surge arrester complies with SPD<br />

class GO.<br />

DRL 10 B 180...<br />

a b a’b’<br />

a a'<br />

TL2 10DA LSA<br />

Disconnection block function<br />

a<br />

a b a’b’<br />

a'<br />

The plug-in SPD block incorporates disconnection contacts that are compatible<br />

with the disconnection block. A measuring or disconnection<br />

adapter can be plugged into the DRL in the same way as a disconnection<br />

block to ensure protection even during maintenance operation.<br />

To protect the gas discharge tube from a possible burn-off due to overcurrent,<br />

a fail-safe function short-circuits the lines to earth. In the event<br />

of an overcurrent, the disconnecting solder between the spring and the<br />

arrester melts, the lines are short-circuited and the temperature-sensitive<br />

colour on the spring changes from light pink to dark purple, indicating<br />

that the arrester must be replaced.<br />

DRL 10 B 180 FSD<br />

fail-safe<br />

light pink<br />

fail-safe<br />

dark purple<br />

ok<br />

replace<br />

Replacement of a faulty gas discharge tube<br />

new<br />