Pluggable DIN Rail Mounted SPD<br />

BLITZDUCTOR ® XT<br />

Lightning current / surge arrester<br />

Max. nominal current at ambient temperature<br />

click<br />

The function-optimised design of the device allows both to safely plug<br />

the protection module into the base part and to remove it without problems.<br />

The module is secured in the base part by snapping it in (audible<br />

click). When pressing the grey buttons, the module can be removed with<br />

little effort. This is ensured by the laminated spring contacts and the<br />

module release spring. A mechanical reverse polarity protection ensures<br />

that the module is installed in the correct position.<br />

2 4<br />

2'4'<br />

1'3'<br />

Nominal current I L in A<br />

2.0<br />

1.9<br />

1.8<br />

1.7<br />

1.6<br />

1.5<br />

1.4<br />

1.3<br />

1.2<br />

1.1<br />

1.0<br />

0.9<br />

0.8<br />

0.7<br />

0.6<br />

0.5<br />

0.4<br />

0.3<br />

0.2<br />

0.1<br />

0.0<br />

– 40<br />

Colour-coded characteristic curves:<br />

BXT ML4 / ML2 ...<br />

BE 5 12 24 36 48 60 180<br />

BD 5 12 24 48 60 180<br />

BC 5 24<br />

BE HF 5<br />

BD HF 5 24<br />

– 20 0 20 40 60 80<br />

Ambient temperature in °C<br />

1 3<br />

Up to 4 lines can be connected on 2 levels. For DIN rail mounting purposes,<br />

lines of a pair belonging to each other are connected on top of one<br />

another.<br />

!<br />

LifeCheck module<br />

BXTU ML2 ... S ...<br />

2<br />

4<br />

1 2 3 4 4´ 3´ 2´ 1´<br />

1<br />

3<br />

Base part<br />

BXT BAS 9<br />

If the line shield cannot be earthed on both sides for technical reasons,<br />

one-sided indirect shield earthing might be advisable. This can be performed<br />

by using protection modules of type BXT ML2 ... S. The terminal<br />

3, 3´ is connected to a gas discharge tube which is capable of carrying<br />

lightning currents and prevents compensating currents. Transient impulse<br />

currents on the shield are discharged via indirect shield earthing.<br />

2’<br />

4’<br />

1’<br />

3’<br />

The protected lines always<br />

have to be assigned to terminals<br />

1´ to 4´ (protected) of<br />

the base part. In order not to<br />

reduce the protective effect,<br />

protected and unprotected<br />

lines have to be installed separately.<br />

protected<br />

ok<br />

Earthing module<br />

BXT M4 E<br />

2<br />

4<br />

1 2 3 4 4´ 3´ 2´ 1´<br />

1<br />

3<br />

Base part<br />

BXT BAS 9<br />

2’<br />

4’<br />

1’<br />

3’<br />

The terminals in the base part can be<br />

used with many two-pole modules for<br />

direct or indirect shield earthing. In particular<br />

in bus systems, it is advisable to<br />

use the EMC spring terminal for largearea<br />

connection of line shields.<br />

In case of a stranded cable, unused lines should be laid and earthed. If<br />

the unused lines are connected to base parts, earthing modules of type<br />

BXT M4 E should be used. These reserve space for retrofitting a protection<br />

module and the lines can be integrated efficiently into the equipotential<br />

bonding.<br />