Protection Module for DEHNbloc ® M<br />

Coordinated Type 1 Lightning Current Arresters<br />

Lightn. Curr. Arr. Type 1<br />

• High discharge capacity due to powerful creepage<br />

discharge spark gap<br />

• Maximum system availability due to RADAX<br />

Flow follow current limitation<br />

• With module release button for replacing protection<br />

modules without tools<br />

• Operating state / fault indication by green / red<br />

indicator flag in the inspection window<br />

• The plug-in protection module can be replaced<br />

without the need to de-energise and removing<br />

the vertical cover<br />

For protecting low-voltage consumer’s installations against surges and<br />

even direct lightning strikes. For installation in conformity with the lightning<br />

protection zones concept at the boundaries from 0 A – 1.<br />

DB M MOD ...: Spark-gap-based protection module<br />

The spark-gap-based protection modules for devices of the DEHNbloc M<br />

family incorporate the complete protective circuit including the RADAX<br />

Flow spark gap and the monitoring circuit for controlling the energy flow.<br />

The spark gap monitoring system and the operating state and fault indicator<br />

are also housed in the protection module.<br />

Every protection module is mechanically coded to ensure against<br />

installing an incorrect replacement module.<br />

As with all modular protective devices, protection modules can be easily<br />

replaced without tools by simply pressing the module release button.<br />

45<br />

36 62<br />

(2 mods.)<br />

Basic circuit diagram DB M MOD ...<br />

Dimension drawing DB M MOD ...<br />

Spark-gap-based protection module<br />

Type DB M MOD 150 DB M MOD 255 DB M MOD 320<br />

Part No. 961 001 961 002 961 003<br />

Max. continuous operating a.c. voltage (U C ) 150 V 255 V 320 V<br />

Lightning impulse current (10/350 μs) (I imp ) 35 kA 50 kA 25 kA<br />

Specific energy (W/R) 306.25 kJ/ohms 625.00 kJ/ohms 156.25 kJ/ohms<br />

961 001<br />

DB M MOD 150<br />

961 002<br />

DB M MOD 255<br />

961 003<br />

DB M MOD 320<br />

DB M MOD 150<br />

961 001<br />

Koordinierter Blitzstromableiter Typ 1 Funkenstrecken-Schutzmodul<br />

DEHNbloc M<br />

DB M MOD 255<br />

961 002<br />

Koordinierter Blitzstromableiter Typ 1 Funkenstrecken-Schutzmodul<br />

DEHNbloc M<br />

DB M MOD 320<br />

961 003<br />

Funkenstrecken-Schutzmodul<br />

für DEHNbloc M<br />

Follow current extinguishing capability a.c. (I fi ) 50 kA rms 50 kA rms 50 kA rms<br />

Follow current limitation/Selectivity<br />

no tripping of a 32 A gL/gG fuse up to 50 kA rms (prosp.)<br />