SPDs for LSA Technology<br />
DEHNrapid ® LSA<br />
DRL RE<br />
a<br />
a<br />
22<br />
9.4<br />
8.5<br />
33.4<br />
IN 9<br />
OUT<br />
1 2 3 4 5 6 7 8 9 0<br />
b<br />
b<br />
Dimension drawing DRL RE<br />
Basic circuit diagram DRL RE<br />
Protective plug (one pair), energy-coordinated with DRL plug-in SPD block, for use as single-stage<br />
protective device for terminal equipment with decoupling impedances. Ideally suited for signal circuits<br />
with common reference potential. Earthing via EF 10 DRL. For disconnection blocks or DRL<br />
plug-in SPD blocks only.<br />
• Low voltage protection level for the<br />
protection of terminal equipment<br />
• Energy-coordinated with DRL plug-in<br />
SPD block<br />
• For installation in conformity with the<br />
lightning protection zones concept at<br />
the boundaries from 1 – 2 and higher<br />
907 420<br />
DRL RE 5<br />
907 421<br />
DRL RE 12<br />
907 422<br />
DRL RE 24<br />
DRL 907 423 RE 5<br />
907 DRL 420 RE 48<br />
Überspannungsableiter 907 424<br />
DEHNrapid LSA Schutzstecker für 1 Doppelader Un<br />
5V DRL RE 60<br />
DRL 907 425 RE 12<br />
907 DRL 421 RE 180<br />
Überspannungsableiter DEHNrapid LSA Schutzstecker für 1 Doppelader Un<br />
12V<br />
DRL RE 24<br />
907 422<br />
Überspannungsableiter DEHNrapid LSA Schutzstecker für 1 Doppelader Un<br />
24V<br />
DRL RE 48<br />
907 423<br />
Überspannungsableiter DEHNrapid LSA Schutzstecker für 1 Doppelader Un<br />
48V<br />
DRL RE 60<br />
907 424<br />
Überspannungsableiter DEHNrapid LSA Schutzstecker für 1 Doppelader Un<br />
60V<br />
DRL RE 180<br />
907 425<br />
Überspannungsableiter DEHNrapid LSA Schutzstecker für 1 Doppelader Un<br />
180V<br />
Type DRL RE 5 DRL RE 12 DRL RE 24 DRL RE 48 DRL RE 60 DRL RE 180<br />
Part No. 907 420 907 421 907 422 907 423 907 424 907 425<br />
SPD class O O O O O O<br />
Nominal voltage (U N ) 5 V 12 V 24 V 48 V 60 V 180 V<br />
Max. continuous operating d.c. voltage (U C ) 6 V 14 V 28 V 54 V 70 V 180 V<br />
Max. continuous operating a.c. voltage (U C ) 4.2 V 9.5 V 19.5 V 38 V 49.5 V 127 V<br />
Nominal current (I L ) 0.4 A 0.4 A 0.4 A 0.4 A 0.4 A 0.1 A<br />
D1 Total lightning impulse current (10/350 μs)<br />
in combination with DRL 10 B... (I imp ) 5 kA 5 kA 5 kA 5 kA 5 kA 5 kA<br />
D1 Lightning impulse current (10/350 μs)<br />
per line in combination with DRL 10 B... (I imp ) 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA 2.5 kA<br />
C2 Total nominal discharge current (8/20 μs)<br />
in combination with DRL 10 B... (I n ) 10 kA 10 kA 10 kA 10 kA 10 kA 10 kA<br />
C2 Nominal discharge current (8/20 μs)<br />
per line in combination with DRL 10 B... (I n ) 5 kA 5 kA 5 kA 5 kA 5 kA 5 kA<br />
Voltage protection level line-PG for I imp D1<br />
in combination with DRL 10 B... (U p ) ≤ 40 V ≤ 45 V ≤ 65 V ≤ 95 V ≤ 115 V ≤ 280 V<br />
Voltage protection level line-line<br />
at 1 kV/μs C3 (U p ) ≤ 17.0 V ≤ 36 V ≤ 72 V ≤ 135 V ≤ 185 V ≤ 500 V<br />
Voltage protection level line-PG<br />
at 1 kV/μs C3 (U p ) ≤ 9.5 V ≤ 19 V ≤ 38 V ≤ 70 V ≤ 95 V ≤ 270 V<br />
Series impedance per line 4.7 ohms 4.7 ohms 4.7 ohms 6.8 ohms 6.8 ohms 4.7 ohms<br />
Cut-off frequency line-PG (f G ) 0.95 MHz 2.7 MHz 4.5 MHz 7.35 MHz 10.5 MHz 42 MHz<br />
Capacitance line-line (C) ≤ 3 nF ≤ 1 nF ≤ 0.55 pF ≤ 350 pF ≤ 250 pF ≤ 50 pF<br />
Capacitance line-PG (C) ≤ 6 nF ≤ 2 nF ≤ 1.1 nF ≤ 700 pF ≤ 500 pF ≤ 80 pF<br />
Operating temperature range -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C<br />
Degree of protection<br />
IP 20 (when plugged in)<br />
Plugs into<br />
LSA disconnection block 2/10 or DRL 10 B ... plug-in SPD block<br />
Earthing via earthing frame earthing frame earthing frame earthing frame earthing frame earthing frame<br />
Enclosure material polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6 polyamide PA 6.6<br />
Colour yellow yellow yellow yellow yellow yellow<br />
Test standards IEC 61643-21 / IEC 61643-21 / IEC 61643-21 / IEC 61643-21 / IEC 61643-21 / IEC 61643-21 /<br />
EN 61643-21 EN 61643-21 EN 61643-21 EN 61643-21 EN 61643-21 EN 61643-21<br />
Approvals VdS, GOST VdS, GOST VdS, GOST VdS, GOST VdS, GOST VdS, GOST<br />
Accessory for DEHNrapid ® LSA<br />
Label Holder<br />
Universal label holder made of stainless steel for clear<br />
identification of LSA connections. Can be snapped onto<br />
DEHNrapid LSA plug-in SPD blocks, earthing frames<br />
with protective plugs or mounting frames with LSA SPD<br />
blocks of 2/10 type.<br />
Type<br />
SR DRL<br />
Part No. 907 497<br />
Material<br />
Stainless steel<br />
Accessory for DEHNrapid ® LSA<br />
Earthing Frame<br />
Snap-on earthing frame for earthing and mounting of<br />
max. 10 DRL protective plugs. Plugs into a 10-pair disconnection<br />
block or DRL plug-in SPD block.<br />
Type<br />
EF 10 DRL<br />
Part No. 907 498<br />
Colour<br />
yellow<br />
www.dehn.de<br />
235