Pluggable DIN Rail Mounted SPDs<br />

BLITZDUCTOR ® XT LifeCheck ® Modules<br />

BXT ML4 BD HF 5 / 24<br />

1<br />

1´<br />

2<br />

2´<br />

45<br />

protected<br />

12 51<br />

(2/3 mods.)<br />

3<br />

4<br />

3´<br />

4´<br />

Dimension drawing BXT ML4 BD HF<br />

Basic circuit diagram BXT ML4 BD HF<br />

Space-saving combined lightning current and surge arrester module with LifeCheck feature for protecting<br />

two pairs in unearthed high-frequency bus systems or video transmission systems. If<br />

LifeCheck detects thermal or electrical overload, the arrester has to be replaced. This status is indicated<br />

contactlessly by the DEHNrecord LC / MCM reader.<br />

• LifeCheck SPD monitoring function<br />

• Minimal signal interference<br />

• For installation in conformity with the<br />

lightning protection zones concept at<br />

the boundaries from 0 A – 2 and higher<br />

920 371<br />

BXT ML4 BD HF 5<br />

920 375<br />

BXT ML4 BD HF 24<br />

BXT ML4 BD HF 5<br />

920 371<br />

Kombiableiter-Modul für 2 DoppeladernBLITZDUCTOR XT mit LifeCheck<br />

BXT ML4 BD HF 24<br />

920 375<br />

Kombiableiter-Modul für 2 DoppeladernBLITZDUCTOR XT mit LifeCheck<br />

Type BXT ML4 BD HF 5 BXT ML4 BD HF 24<br />

Part No. 920 371 920 375<br />

SPD class M M<br />

SPD monitoring system LifeCheck LifeCheck<br />

Nominal voltage (U N ) 5 V 24 V<br />

Max. continuous operating d.c. voltage (U C ) 6.0 V 33 V<br />

Max. continuous operating a.c. voltage (U C ) 4.2 V 23.3 V<br />

Nominal current at 45°C (I L ) 1.0 A 1.0 A<br />

D1 Total lightning impulse current (10/350 μs) (I imp ) 10 kA 10 kA<br />

D1 Lightning impulse current (10/350 μs) per line (I imp ) 2.5 kA 2.5 kA<br />

C2 Total nominal discharge current (8/20 μs) (I n ) 20 kA 20 kA<br />

C2 Nominal discharge current (8/20 μs) per line (I n ) 10 kA 10 kA<br />

Voltage protection level line-line for I imp D1 (U p ) ≤ 25 V ≤ 65 V<br />

Voltage protection level line-PG for I imp D1 (U p ) ≤ 550 V ≤ 550 V<br />

Voltage protection level line-line at 1 kV/μs C3 (U p ) ≤ 11 V ≤ 47 V<br />

Voltage protection level line-PG at 1 kV/μs C3 (U p ) ≤ 550 V ≤ 550 V<br />

Series impedance per line 1.0 ohm 1.0 ohm<br />

Cut-off frequency line-line (f G ) 100.0 MHz 100,0 MHz<br />

Capacitance line-line (C) ≤ 25 pF ≤ 25 pF<br />

Capacitance line-PG (C) ≤ 16 pF ≤ 16 pF<br />

Operating temperature range -40°C...+80°C -40°C...+80°C<br />

Degree of protection (with plugged-in protection module) IP 20 IP 20<br />

Pluggable into base part base part<br />

Earthing via base part base part<br />

Enclosure material polyamide PA 6.6 polyamide PA 6.6<br />

Colour yellow yellow<br />

Test standards IEC 61643-21 / EN 61643-21, UL 497B IEC 61643-21 / EN 61643-21, UL 497B<br />

SIL classification SIL2 * ) SIL2 * )<br />

ATEX approvals DEKRA 11ATEX0089 X: II 3 G Ex nA IIC T4 Gc DEKRA 11ATEX0089 X: II 3 G Ex nA IIC T4 Gc<br />

IECEx approvals DEK 11.0032X: Ex nA IIC T4 Gc DEK 11.0032X: Ex nA IIC T4 Gc<br />

Approvals CSA, VdS, UL, GOST CSA, VdS, UL, GOST<br />

*) For more detailed information, please refer to www.dehn.de/en/sil/ and page 210<br />

Accessories for BLITZDUCTOR ® XT LifeCheck ® Modules<br />

Labelling system BA1-BA15<br />

2x165 adhesive labels for labelling<br />

DRC MCM XT monitoring devices<br />

with their bus address.<br />

Type BS BA1 BA15 BXT<br />

Part No. 920 398<br />

Colour<br />

white<br />

Earthing module<br />

For direct earthing of lines connected<br />

to the BLITZDUCTOR XT<br />

base part.<br />

Type<br />

BXT M4 E<br />

Part No 920 308<br />

Colour<br />

grey<br />

Test / Disconnection module<br />

Module for testing lines, plugs into<br />

BLITZDUCTOR XT base parts<br />

Type<br />

BXT M4 T<br />

Part No 920 309<br />

Colour<br />

grey<br />

For ”Accessories for BLITZDUCTOR XT LifeCheck modules“, please also refer to pages 188/206/207/208/368/370.<br />