Type 2 Surge Arresters<br />

DEHNguard ® modular<br />

DEHNguard M TT ...<br />

30<br />

L1<br />

L2<br />

L3<br />

N<br />

L1 L2 L3 N<br />

90<br />

45<br />

72<br />

(4 mods.)<br />

PE<br />

7<br />

43.5<br />

66<br />

Dimension drawing DG M TT ...<br />

Modular surge arrester for use in TT and TN-S systems ("3+1" circuit)<br />

9<br />

PE<br />

Basic circuit diagram DG M TT ...<br />

• Prewired complete unit consisting of a<br />

base part and plug-in protection modules<br />

• High discharge capacity due to heavyduty<br />

zinc oxide varistors/spark gaps<br />

• High reliability due to "Thermo Dynamic<br />

Control" SPD monitoring device<br />

952 323<br />

DG M TT 150<br />

952 310<br />

DG M TT 275<br />

952 320<br />

DG M TT 320<br />

DG 952 M 311 TT 150<br />

952 DG M 323 TT 385<br />

Überspannungsableiter Typ 2 DEHNguard M 4-polig für TT- und TN-S-<br />

Systeme<br />

DG M TT 275<br />

952 310<br />

Überspannungsableiter Typ 2 DEHNguard M 4-polig für TT- und TN-S-<br />

Systeme<br />

DG M TT 320<br />

952 320<br />

Überspannungsableiter Typ 2 DEHNguard M 4-polig für TT- und TN-S-<br />

Systeme<br />

DG M TT 385<br />

952 311<br />

Überspannungsableiter Typ 2 DEHNguard M 4-polig für TT- und TN-S-<br />

Systeme<br />

Type DG M TT 150 DG M TT 275 DG M TT 320 DG M TT 385<br />

Part No. 952 323 + 952 310 952 320 952 311<br />

SPD according to EN 61643-11 Type 2 Type 2 Type 2 Type 2<br />

SPD according to IEC 61643-1/-11 Class II Class II Class II Class II<br />

Nominal a.c. voltage (U N ) 120/240 V 230/400 V 230/400 V 230/400 V<br />

Max. continuous operating a.c. voltage [L-N] (U C ) 150 V 275 V 320 V 385 V<br />

Max. continuous operating a.c. voltage [N-PE] (U C ) 255 V 255 V 255 V 255 V<br />

Nominal discharge current (8/20 μs) (I n ) 15 kA 20 kA 20 kA 20 kA<br />

Max. discharge current (8/20 μs) (I max ) 40 kA 40 kA 40 kA 40 kA<br />

Lightning impulse current (10/350 μs) [N-PE] (I imp ) 12 kA 12 kA 12 kA 12 kA<br />

Voltage protection level [L-N] (U P ) ≤ 0.7 kV ≤ 1.25 kV ≤ 1.5 kV ≤ 1.75 kV<br />

Voltage protection level [L-N] at 5 kA (U P ) ≤ 0.55 kV ≤ 1 kV ≤ 1.2 kV ≤ 1.35 kV<br />

Voltage protection level [N-PE] (U P ) ≤ 1.5 kV ≤ 1.5 kV ≤ 1.5 kV ≤ 1.5 kV<br />

Follow current extinguishing capability [N-PE] (I fi ) 100 A rms 100 A rms 100 A rms 100 A rms<br />

Response time [L-N] (t A ) ≤ 25 ns ≤ 25 ns ≤ 25 ns ≤ 25 ns<br />

Response time [N-PE] (t A ) ≤ 100 ns ≤ 100 ns ≤ 100 ns ≤ 100 ns<br />

Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG 125 A gL/gG<br />

Short-circuit withstand capability for max.<br />

mains-side overcurrent protection 50 kA rms 50 kA rms 25 kA rms 25 kA rms<br />

Temporary overvoltage (TOV) [L-N] (U T ) 175 V / 5 sec. 335 V / 5 sec. 335 V / 5 sec. 385 V / 5 sec.<br />

Temporary overvoltage (TOV) [N-PE] (U T ) 1200 V / 200 ms 1200 V / 200 ms 1200 V / 200 ms 1200 V / 200 ms<br />

TOV characteristics withstand withstand withstand withstand<br />

Operating temperature range (T U ) -40°C...+80°C -40°C...+80°C -40°C...+80°C -40°C...+80°C<br />

Operating state/fault indication green / red green / red green / red green / red<br />

Number of ports 1 1 1 1<br />

Cross-sectional area (min.)<br />

1.5 mm 2 solid/flexible<br />

Cross-sectional area (max.)<br />

35 mm 2 stranded/25 mm 2 flexible<br />

For mounting on 35 mm DIN rail acc. to EN 60715<br />

Enclosure material thermoplastic, red, UL 94 V-0<br />

Place of installation indoor installation indoor installation indoor installation indoor installation<br />

Degree of protection IP 20 IP 20 IP 20 IP 20<br />

Capacity 4 modules, DIN 43880 4 modules, DIN 43880 4 modules, DIN 43880 4 modules, DIN 43880<br />

Approvals –– KEMA, VDE, UL, VdS KEMA KEMA, UL<br />

Surge Arresters Type 2<br />

Accessory for DEHNguard ® modular<br />

N-PE Spark-Gap-Based Protection Module<br />

for DEHNguard M TT ...<br />

N-PE spark-gap-based protection module for two-pole<br />

and four-pole DEHNguard DG M TT ... surge arresters<br />

Type<br />

DG MOD NPE<br />

Part No. 952 050<br />

Max. continuous operating a.c. voltage (U C ) 255 V<br />

Accessory for DEHNguard ® modular<br />

Varistor-Based Protection Module<br />

Varistor-base protection module for DEHNguard M ...<br />

and DEHNguard S ... surge arresters<br />

Type DG MOD ... 150 275 320 385<br />

Part No. 952 012 952 010 952 013 952 014<br />

Max. continuous operating<br />

a.c. voltage (U C ) 150 V 275 V 320 V 385 V<br />

www.dehn.de<br />