Type 2 Surge Arresters<br />

DEHNguard ® modular<br />

DEHNguard M TN ...<br />

30<br />

L<br />

N<br />

L<br />

N<br />

90<br />

45<br />

36 7<br />

(2 mods.)<br />

PE<br />

43.5<br />

66<br />

9<br />

PE<br />

Dimension drawing DG M TN ...<br />

Modular surge arrester for use in single-phase TN systems<br />

Basic circuit diagram DG M TN ...<br />

• Prewired complete unit consisting of a<br />

base part and plug-in protection modules<br />

• High discharge capacity due to heavyduty<br />

zinc oxide varistors/spark gaps<br />

• High reliability due to "Thermo Dynamic<br />

Control" SPD monitoring device<br />

952 201<br />

DG M TN 150<br />

952 200<br />

DG M TN 275<br />

DG M TN 150<br />

952 201<br />

Überspannungsableiter Typ 2 DEHNguard M für einphasige TN-Systeme<br />

DG M TN 275<br />

952 200<br />

Überspannungsableiter Typ 2 DEHNguard M für einphasige TN-Systeme<br />

Type DG M TN 150 DG M TN 275<br />

Part No. 952 201 952 200<br />

SPD according to EN 61643-11 Type 2 Type 2<br />

SPD according to IEC 61643-1/-11 Class II Class II<br />

Nominal a.c. voltage (U N ) 120 V 230 V<br />

Max. continuous operating a.c. voltage (U C ) 150 V 275 V<br />

Nominal discharge current (8/20 μs) (I n ) 15 kA 20 kA<br />

Max. discharge current (8/20 μs) (I max ) 40 kA 40 kA<br />

Voltage protection level (U P ) ≤ 0.7 kV ≤ 1.25 kV<br />

Voltage protection level at 5 kA (U P ) ≤ 0.55 kV ≤ 1 kV<br />

Response time (t A ) ≤ 25 ns ≤ 25 ns<br />

Max. mains-side overcurrent protection 125 A gL/gG 125 A gL/gG<br />

Short-circuit withstand capability for max. mains-side overcurrent protection 50 kA rms 50 kA rms<br />

Temporary overvoltage (TOV) (U T ) 175 V / 5 sec. 335 V / 5 sec.<br />

TOV characteristics withstand withstand<br />

Operating temperature range (T U ) -40°C...+80°C -40°C...+80°C<br />

Operating state/fault indication green / red green / red<br />

Number of ports 1 1<br />

Cross-sectional area (min.) 1.5 mm 2 solid/flexible 1.5 mm 2 solid/flexible<br />

Cross-sectional area (max.) 35 mm 2 stranded/25 mm 2 flexible 35 mm 2 stranded/25 mm 2 flexible<br />

For mounting on 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715<br />

Enclosure material thermoplastic, red, UL 94 V-0 thermoplastic, red, UL 94 V-0<br />

Place of installation indoor installation indoor installation<br />

Degree of protection IP 20 IP 20<br />

Capacity 2 modules, DIN 43880 2 modules, DIN 43880<br />

Approvals KEMA, UL KEMA, VDE, UL, VdS<br />

Surge Arresters Type 2<br />

Accessory for DEHNguard ® modular<br />

Varistor-Based Protection Module<br />

Varistor-based protection module for DEHNguard M ...<br />

and DEHNguard S ... surge arresters<br />

Type DG MOD ... 150 275<br />

Part No. 952 012 952 010<br />

Max. continuous operating<br />

a.c. voltage (U C ) 150 V 275 V<br />

www.dehn.de<br />