142 M16: FIRE DESIGN<br />

type of assembly being penetrated: F signifies a floor, W<br />

signifies a wall, and C signifies a ceiling. The second alpha<br />

signifies a limiting description, for example: C signifies a<br />

framed floor, and L signifies a framed wall. The numeric<br />

portion is also significant: 0000-0999 signifies no penetrating<br />

items, 1000-1999 signifies metallic pipe, 2000-2999<br />

signifies nonmetallic pipe, 3000-3999 signifies electrical<br />

cable, 4000-4999 signifies cable trays, 5000-5999 signifies<br />

insulated pipes, 6000-6999 signifies miscellaneous<br />

electrical penetrants, 7000-7999 signifies miscellaneous<br />

mechanical penetrants, and 8000-8999 signifies a combination<br />

of penetrants.<br />

For example, a floor/ceiling penetrated by a metallic<br />

pipe would have a designation of F-C-1xxx, or with<br />

nonmetallic pipe would be designated F-C-2xxx. A few<br />

examples of floor/ceiling penetrations are included below.<br />

Examples in Figure M16.1-23 are from the UL Fire Resistance<br />

Directory, Vol. II: UL Systems F-C-2008, F-C-1006,<br />

F‐C‐3007 & 8, F-C-5002.<br />

Figure M16.1-23 Examples of Through-Penetration Firestop Systems<br />

UL F-C-2008<br />

Firestop<br />

system<br />

F-Rating - 1 Hr<br />

Pipe or Conduit<br />

T-Rating - 1 Hr<br />

F-Rating - 1 Hr<br />

T-Rating - 1 Hr<br />

UL F-C-3007<br />

General assembly<br />

General<br />

assembly<br />

Firestop<br />

system<br />

Firestop<br />

system<br />

Cables<br />

F-Rating - 1 Hr<br />

T-Rating - 1 Hr<br />

Pipe or Conduit<br />

F-Rating - 1 Hr<br />

T-Rating - 1 Hr<br />

UL F-C-3008<br />

Firestop<br />

system<br />

General<br />

assembly<br />

Cables<br />

General<br />

assembly<br />

Firestop<br />

system<br />

F-Rating - 1 Hr<br />

T-Rating - 1 Hr<br />

Firestop<br />

system<br />

UL F-C-1006<br />

Pipe or<br />

Conduit<br />

General<br />

assembly<br />

F-Rating - 1 Hr<br />

T-Rating - 1 Hr<br />

UL F-C-5002<br />

Firestop<br />

system<br />

Schedule<br />

10 Steel or<br />

copper pipe<br />

with pipe covering<br />

General<br />

assembly<br />

<strong>American</strong> <strong>Wood</strong> <strong>Council</strong>