142 M16: FIRE DESIGN<br />
type of assembly being penetrated: F signifies a floor, W<br />
signifies a wall, and C signifies a ceiling. The second alpha<br />
signifies a limiting description, for example: C signifies a<br />
framed floor, and L signifies a framed wall. The numeric<br />
portion is also significant: 0000-0999 signifies no penetrating<br />
items, 1000-1999 signifies metallic pipe, 2000-2999<br />
signifies nonmetallic pipe, 3000-3999 signifies electrical<br />
cable, 4000-4999 signifies cable trays, 5000-5999 signifies<br />
insulated pipes, 6000-6999 signifies miscellaneous<br />
electrical penetrants, 7000-7999 signifies miscellaneous<br />
mechanical penetrants, and 8000-8999 signifies a combination<br />
of penetrants.<br />
For example, a floor/ceiling penetrated by a metallic<br />
pipe would have a designation of F-C-1xxx, or with<br />
nonmetallic pipe would be designated F-C-2xxx. A few<br />
examples of floor/ceiling penetrations are included below.<br />
Examples in Figure M16.1-23 are from the UL Fire Resistance<br />
Directory, Vol. II: UL Systems F-C-2008, F-C-1006,<br />
F‐C‐3007 & 8, F-C-5002.<br />
Figure M16.1-23 Examples of Through-Penetration Firestop Systems<br />
UL F-C-2008<br />
Firestop<br />
system<br />
F-Rating - 1 Hr<br />
Pipe or Conduit<br />
T-Rating - 1 Hr<br />
F-Rating - 1 Hr<br />
T-Rating - 1 Hr<br />
UL F-C-3007<br />
General assembly<br />
General<br />
assembly<br />
Firestop<br />
system<br />
Firestop<br />
system<br />
Cables<br />
F-Rating - 1 Hr<br />
T-Rating - 1 Hr<br />
Pipe or Conduit<br />
F-Rating - 1 Hr<br />
T-Rating - 1 Hr<br />
UL F-C-3008<br />
Firestop<br />
system<br />
General<br />
assembly<br />
Cables<br />
General<br />
assembly<br />
Firestop<br />
system<br />
F-Rating - 1 Hr<br />
T-Rating - 1 Hr<br />
Firestop<br />
system<br />
UL F-C-1006<br />
Pipe or<br />
Conduit<br />
General<br />
assembly<br />
F-Rating - 1 Hr<br />
T-Rating - 1 Hr<br />
UL F-C-5002<br />
Firestop<br />
system<br />
Schedule<br />
10 Steel or<br />
copper pipe<br />
with pipe covering<br />
General<br />
assembly<br />
<strong>American</strong> <strong>Wood</strong> <strong>Council</strong>