Chapter 10: Graph Display<br />
[1] Trend Graph (corresponds to page 10-27)<br />
[Trend] Dialog<br />
[Setting 3] Tab Window<br />
Two lines are added to both upper line and lower line.<br />
This menu is available when [Upper Line 2 Display] or [Lower Line 2 Display] is clicked. The<br />
properties like [Data Length] or [Graph Max./Min.] are specified in the [Setting 2] tab window.<br />
The settings are the same as the present [Upper/Lower Line].<br />
<br />
(Upper Line 2)<br />
(Upper Line)<br />
(Lower Line)<br />
(Lower Line 2)<br />
Asynchronous Display of Multiple Trend Graphs (corresponds to page 10-27)<br />
In the <strong>ZM</strong>80, all the trends on a trend graph is displayed to the same points at the same timing,<br />
because a trend graph has only one control memory.<br />
If you want to display each trend at the asynchronous timing, you have to make another trend<br />
graph to overlap the original trend graph for setting another control memory.<br />
However, it may be that the trends are deleted or displayed at every redrawing by the [Redraw]<br />
bit or the [Redraw after clear] bit to give the order of each control memory priority.<br />
To avoid the above condition, the order of priority for each control memory is decided by linking<br />
two or more overlapped trend graphs.<br />
For example, when drawing two trend graphs as follows;<br />
Division No. : 0<br />
Control Memory : D120<br />
Process Cycle : High Speed<br />
(=Master Trend Graph)<br />
1) D120 = H0009<br />
(Number of trend counts)<br />
2) D140 = K9<br />
(Number of trend counts)<br />
Division No. : 1<br />
Control Memory : D140<br />
Use Link<br />
Link Division No.<br />
Process Cycle : High Speed<br />
(=Slave Trend Graph)<br />
3) D140 = K5<br />
(Number of trend counts)<br />
D120 = H8007<br />
(Redraw after clear<br />
/ Number of trend counts)<br />
The master trend graph is<br />
drawn at the 9 points.<br />
The slave trend graph is<br />
drawn at the 9 points.<br />
<br />
Change the number of counts to<br />
5 points in the slave trend graph,<br />
and send both changing the<br />
number of counts to 7 points and<br />
the [Read after clear] command<br />
in the master trend graph at the<br />
same time. At the same time,<br />
the 5 points of the trends in the<br />
slave trend graph is drawn.