05.06.2015 Views

ZM-71SE About version 1.2.1.0 - Soliton

ZM-71SE About version 1.2.1.0 - Soliton

ZM-71SE About version 1.2.1.0 - Soliton

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Chapter 10: Graph Display<br />

[1] Trend Graph (corresponds to page 10-27)<br />

[Trend] Dialog<br />

[Setting 3] Tab Window<br />

Two lines are added to both upper line and lower line.<br />

This menu is available when [Upper Line 2 Display] or [Lower Line 2 Display] is clicked. The<br />

properties like [Data Length] or [Graph Max./Min.] are specified in the [Setting 2] tab window.<br />

The settings are the same as the present [Upper/Lower Line].<br />

<br />

(Upper Line 2)<br />

(Upper Line)<br />

(Lower Line)<br />

(Lower Line 2)<br />

Asynchronous Display of Multiple Trend Graphs (corresponds to page 10-27)<br />

In the <strong>ZM</strong>80, all the trends on a trend graph is displayed to the same points at the same timing,<br />

because a trend graph has only one control memory.<br />

If you want to display each trend at the asynchronous timing, you have to make another trend<br />

graph to overlap the original trend graph for setting another control memory.<br />

However, it may be that the trends are deleted or displayed at every redrawing by the [Redraw]<br />

bit or the [Redraw after clear] bit to give the order of each control memory priority.<br />

To avoid the above condition, the order of priority for each control memory is decided by linking<br />

two or more overlapped trend graphs.<br />

For example, when drawing two trend graphs as follows;<br />

Division No. : 0<br />

Control Memory : D120<br />

Process Cycle : High Speed<br />

(=Master Trend Graph)<br />

1) D120 = H0009<br />

(Number of trend counts)<br />

2) D140 = K9<br />

(Number of trend counts)<br />

Division No. : 1<br />

Control Memory : D140<br />

Use Link<br />

Link Division No.<br />

Process Cycle : High Speed<br />

(=Slave Trend Graph)<br />

3) D140 = K5<br />

(Number of trend counts)<br />

D120 = H8007<br />

(Redraw after clear<br />

/ Number of trend counts)<br />

The master trend graph is<br />

drawn at the 9 points.<br />

The slave trend graph is<br />

drawn at the 9 points.<br />

<br />

Change the number of counts to<br />

5 points in the slave trend graph,<br />

and send both changing the<br />

number of counts to 7 points and<br />

the [Read after clear] command<br />

in the master trend graph at the<br />

same time. At the same time,<br />

the 5 points of the trends in the<br />

slave trend graph is drawn.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!